Plan Review Notes For Permit 02051638 |
Permit Number |
02051638 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-12 00:00:00 | PROVISO:MECHANICAL PERMIT 02051703 | | | | APPLIANCES SHALL NOT BE INSTALLED IN A | | LOCATION WHERE SUBJECT TO MECHANICAL | | DAMAGE UNLESS PROTECTED BY APPROVED | | BARRIERS.2001 FBC(M) 303.4 | | | | SHOULD DRYERS BE GAS - | | SHOW COMPLIANCE FOR COMBUSTION AIR AS | | PER 2001 FBC(M) CHAPTER 7. | | | | ADDITIONAL PERMIT REQUIRED FOR GAS, | | PLEASE PROVIDE PLANS SHOWING DEVELOPED | | LENGTH & BTUS FOR APPLIANCES. | | | | SMOKE DETECTORS SHALL BE INSTALLED IN | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | AIR DUCT. 2001 FBC(M) 606.2.1 | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | WITH NOTIFICATION TO ALARM/STOBE OR AREA | | SMOKE DETECTORS. 2001 FBC(M) 606.4.1 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|