Plan Review Notes
Plan Review Notes For Permit 02051565
Permit Number 02051565
Review Stop P
Sequence Number 1
Notes
Date Text
2002-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE. TUB AND SHOWER ARE NOT VENTED.
 2) SHT 4 NOTES #8 AND #13. 1/4" PER FOOT
 SLOPE REQUIRED FOR 2-1/2" AND SMALLER
 PIPE. - AIR CHAMBERS ARE NOT APPROVED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377