Plan Review Notes For Permit 02051561 |
Permit Number |
02051561 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-26 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE NO INFORMATION IS | | SHOWN FOR NEW PANEL. SIZE?? | | | | 2)NOTE: PLEASE NOTE MEANS OF DISC FOR | | DETACHED STRUCTURE PER 225-31 | | DISC? MCB? | | | | 3)NOTE: PLEASE CLARIFY GROUNDING OF NEW | | TRANSFORMER PER 250-30 | | | | 4)NOTE: PLEASE ALSO NOTE COLD WATER PIPE | | AT DETACHED BLDG TO BE BONDED. PLEASE | | SHOW. 250-32 | | | | 5)NOTE: PLEASE NOTE PLANS MENTIONS SEE | | NOTE "F" AND NO NOTE "F" IS SHOWN? | | PLEASE CLARIFY. | | | | 6)NOTE: PLEASE VERIFY 240-21-C-4 | | MUST MEET ALL EXPT. | | | | 7)NOTE: PLEASE VERIFY USE OF GARAGE/ | | USED FOR STORAGE OF VEHICLES ONLY? | | NO WORKING ON VEHICLES? NEC 511-2 | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | REVIEW. IF THEREARE ANY QUESTINS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|