Plan Review Notes For Permit 02051528 |
Permit Number |
02051528 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-08 00:00:00 | PASS/PRIVISO | | 1) NEED REVISED PLAN AT FINAL | | 2) VARIFY TYPE OF VENTILATION USED FOR | | FRESH AIR NATURAL SECTION 402 FBC.OR | | MECHANICAL SECTION 403 FBC. | | 3) NEED CALCULATIONS FOR TYPE OF | | VENTILATION USED | | 4) NEED FAN SHUTDOWN FOR FINAL | | INSPECTION SECTION 606.2.1 FBC. | | 5) CONDENSATE DRAIN MUST TERMINATE 12IN | | FROM BUILDING SECTION 1503.4.4 | | PLAN REVIEW BY HAROLD MOSER | | (561)659-8096 EXT.8390 |
|