Plan Review Notes
Plan Review Notes For Permit 02051381
Permit Number 02051381
Review Stop M
Sequence Number 1
Notes
Date Text
2002-06-08 00:00:00PASS/PRIVISO
 1)VARIFY TYPE OF VENTILATION USED FOR
 FRESH AIR.NATURAL SECTION 402
 MECHANICAL SECTION 403.2001 FBC.
 2) CALCULATIONS FOR TYPE OF
 VENTILATION USED
 3) NEED FAN SHUTDOWN FOR FINAL
 INSPECTION SECTION 606.2.1 FBC.
 4) CONDENSATE DRAIN MUST TERMINATE 12IN.
 FROM BUILDING SECTION 1503.4.4 FBC.
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390