Plan Review Notes
Plan Review Notes For Permit 02051361
Permit Number 02051361
Review Stop M
Sequence Number 1
Notes
Date Text
2002-05-29 00:00:00PROVISO:
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 PRESSURE DIFFERNTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001" WC OR
 LESS. PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE
 ZONE TO THE LOW ZONE.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 PLEASE NOTE, IF SECONDARY DRAIN IS USED
 AT THE AUXILIARY DRAIN PAN, IT SHALL
 TERMINATE AT A CONSPICUOUS POINT AS PER
 2001 FBC(M) 307.2.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.