Plan Review Notes For Permit 02050945 |
Permit Number |
02050945 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-05-20 00:00:00 | PROVISO: | | | | PRESSURE DIFFERENTIALS ACROSS CLOSED | | DOORS WHERE RETURNS ARE CENTRALLY | | LOCATED SHALL BE LIMITED TO .001 INCH | | WC OR LESS. PROVIDE AIR DUCT PATHWAYS OR | | AIR TRANSFER PATHWAYS FROM THE HIGH | | PRESSURE ZONE TO THE LOW ZONES. | | 2001 FBC(M) 601.4. | | | | CONDENSATE SHALL DISCHARGE AWAY FROM | | THE BUILDING STRUCTURE A MINIMUM OF 12 | | INCHES.2001 FBC 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|