2002-05-20 00:00:00PROVISO:
  
 PRESSURE DIFFERENTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001 INCH
 WC OR LESS. PROVIDE AIR DUCT PATHWAYS OR
 AIR TRANSFER PATHWAYS FROM THE HIGH
 PRESSURE ZONE TO THE LOW ZONES.
 2001 FBC(M) 601.4.
  
 CONDENSATE SHALL DISCHARGE AWAY FROM
 THE BUILDING STRUCTURE A MINIMUM OF 12
 INCHES.2001 FBC 1503.4.4.
  