Plan Review Notes
Plan Review Notes For Permit 02050855
Permit Number 02050855
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-05-17 00:00:001) CLEARANCES TO FIRE HYDRANTS MUST BE
 AT LEAST SEVEN AND HALF FEET TO THE
 FRONT AND SIDES OF THEM. FOUR FEET
 CLEARANCE IS TO BE PROVIDED TO THE
 REAR OF THEM. RE: FFPC 3-5.6.2.1
  
 2) THE ABOVE CLEARANCES ARE TO BE
 PROVIDED TO FIRE PROTECTION APPLIANCES.
  
 3) APPROPRIATE SIGNAGE IS TO BE PROVIDED
 "NO PARKING, FIRE DEPARTMENT CONNECTION"
 IN ACCORDANCE WITH DOT STANDARDS FOR
 INFORMATION SIGNAGE. RE: FFPC 3-5.6.2.3
  
 4) ELECTRONIC SWITCHES WILL BE REQUIRED
 ON FIRE LINE BACKFLOW DEVICES.
  
 5) WET FIRE HDYRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910