Date |
Text |
2002-07-24 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) PLEASE INDICATE THE ROOF SHEATHING |
| NAILING SPECIFICATIONS ON THE PLANS. |
| |
| 3) IN THE DESIGN LOADS INFORMATION ON |
| PAGE 2 OF YOUR SIGNED AND SEALED LETTER |
| THE COMPRESSIVE STRENGTH OF THE MASONRY |
| UNITS IS GIVEN AS 1900 PSI AND ON SHEET |
| 2 OF THE PLANS IT IS LISTED AS 1000 PSI. |
| PLEASE CLARIFY. |
| |
| 4) THE COMPONENTS AND CLADDING LISTED |
| ON SHEET 2 UNDER ROOF GIVES MAXIMUM |
| WINDLOAD PRESSURES AS +20.3 AND -68.1 |
| PSF & THE WORST CASE HURRICANE SHUTTER |
| LOADS ARE GIVEN AS +35.3 AND -47.2 PSF. |
| PLEASE INDICATE THE WINDLOAD PRESSURES |
| FOR THE WINDOW AND DOOR OPENINGS OF THE |
| STRUCTURE. (SEE ITEM # 5 ON PREVIOUS |
| REVIEW COMMENTS.) |
| |
| 5) THE NOTE JUST BELOW THE HURRICANE |
| SHUTTER INFORMATION STATES THAT TAPCON |
| INSTALLATIONS ARE BASED ON SIMPSON TITEN |
| MASONRY SCREW ANCHORS. PLEASE SPECIFY |
| WHICH INSTALLATIONS YOU ARE REFERING TO. |
| THIS SHOULD NOT BE REFERING TO THE |
| INSTALLATION OF THE HURRICANE PANELS, AS |
| YOU HAVE INDICATED IN ITEM #1 OF YOUR |
| LETTER THAT YOU WILL BE USING ONLY THE |
| RAWL CALK-IN ANCHORS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |