2002-07-24 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PLEASE INDICATE THE ROOF SHEATHING
 NAILING SPECIFICATIONS ON THE PLANS.
  
 3) IN THE DESIGN LOADS INFORMATION ON
 PAGE 2 OF YOUR SIGNED AND SEALED LETTER
 THE COMPRESSIVE STRENGTH OF THE MASONRY
 UNITS IS GIVEN AS 1900 PSI AND ON SHEET
 2 OF THE PLANS IT IS LISTED AS 1000 PSI.
 PLEASE CLARIFY.
  
 4) THE COMPONENTS AND CLADDING LISTED
 ON SHEET 2 UNDER ROOF GIVES MAXIMUM
 WINDLOAD PRESSURES AS +20.3 AND -68.1
 PSF & THE WORST CASE HURRICANE SHUTTER
 LOADS ARE GIVEN AS +35.3 AND -47.2 PSF.
 PLEASE INDICATE THE WINDLOAD PRESSURES
 FOR THE WINDOW AND DOOR OPENINGS OF THE
 STRUCTURE. (SEE ITEM # 5 ON PREVIOUS
 REVIEW COMMENTS.)
  
 5) THE NOTE JUST BELOW THE HURRICANE
 SHUTTER INFORMATION STATES THAT TAPCON
 INSTALLATIONS ARE BASED ON SIMPSON TITEN
 MASONRY SCREW ANCHORS. PLEASE SPECIFY
 WHICH INSTALLATIONS YOU ARE REFERING TO.
 THIS SHOULD NOT BE REFERING TO THE
 INSTALLATION OF THE HURRICANE PANELS, AS
 YOU HAVE INDICATED IN ITEM #1 OF YOUR
 LETTER THAT YOU WILL BE USING ONLY THE
 RAWL CALK-IN ANCHORS.
  