2002-07-11 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE UNIT NUMBERS ON THE STORM PANEL
 INSTALLATION ARE NOT TIED TO THE KEY
 PLAN. PLEASE NUMBER THE OPENINGS ON THE
 KEY PLAN TO CORRESPOND WITH THE UNIT
 NUMBERS ON THE SCHEDULE.
  
 3) THE STORM PANEL ANCHOR TABLE ON SHEET
 3 OF THE PRODUCT APPROVAL REQUIRES A
 MINIMUM OF 3320 PSI CONCRETE FOR TAPCONS
 AND 1598 PSI CONCRETE BLOCK FOR TAPCONS
 OR RAWL CALK-IN ANCHORS. THE PLANS
 SPECIFY 3000 PSI CONCRETE AND 1000 PSI
 MASONRY UNITS ON SHEET 2. PLEASE REVISE.
  
 4) PROVIDE A ROOF NAILING SCHEDULE.
 INDICATE THE FASTENING REQUIREMENTS FOR
 ZONES 1,2,AND 3. SEE TABLE 2306.1 OF
 CITY AMENDMENTS TO THE 2001 FBC.
  
 5) THE ROOF CHART ON SHEET 6 LISTS THE
 MAXIMUM PRESSURES FOR COMPONENTS AND
 CLADDING AS + 20.3 AND - 68.1.
  
 A) THE NEGATIVE DESIGN PRESSURES LISTED
 IN THE PRODUCT APPROVALS FOR SEVERAL OF
 THE SINGLE HUNG WINDOW SIZES ARE
 EXCEEDED.
  
 B) THE NEGATIVE DESIGN PRESSURE FOR THE
 FRONT DOOR IS ALSO EXCEEDED.
  
 C) THE 1/2 ROUND FIXED GLASS WINDOWS
 WILL BE REQUIRED TO BE TEMPERED GLASS IN
 ORDER TO WITHSTAND THE WINDLOAD
 PRESSURES GIVEN ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202