Plan Review Notes For Permit 02050813 |
Permit Number |
02050813 |
|
Review Stop |
R |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-07-17 00:00:00 | THE REVISIONS SUBMITTED JULY 15, 2002 | | HAVE THE WRONG ADDRESS. | | | | THE LETTERS REVISING THE WIND PRESSURES | | FOR THE COMPONENTS AND CLADDING DOES NOT | | HAVE THE ARCHITECT'S EMBOSSED SEAL IN | | ACCORDANCE WITH FBC 104.2.2. | | | | THE FLOOR PLAN FOR THE SHUTTERS DOES NOT | | HAVE THE OPENINGS NUMBERED TO DESIGNATE | | LOCATION. | | | | THE SHUTTER INFORMATION DOES NOT HAVE | | THE EMBOSSED SEAL OF THE DESIGNER OF | | RECORD.FBC 104.2.2. | | | | IT WAS NOTED AT TIME OF PERMIT ISSUE | | FORTHE HOUSE, THAT A SEPARATE PERMIT | | AND FEES WOULD BE REQUIRED FOR THE | | WINDOWS, DOORS, SHUTTERS, ETC. BECAUSE | | THE TEST REPORTS PROVIDED AT THAT TIME | | DID NOT MEET THE DECLARED WIND | | PRESSURES ON THE PERMIT PLANS. | | | | PLEASE PROVIDE A PERMIT FOR THE VALUE OF | | THIS PROPOSED WORK, WITH THE | | INFORMATION CORRECTED AS ABOVE, | | SUBSEQUENT TO OR CONCURRENTLY WITH THE | | REVISIONS CHANGING THE DESIGN WIND | | PRESSURES. |
|