2002-06-17 00:00:00SECTION 1/A ON SHEET A MAKES REFERENCE
 TO THE HEADER TABLES IN FBC. FBC
 104.2.1 SPEAKS TO PROVIDNG SPECIFIC
 DESIGN DATA AND NOT REFERENCING CODE
 SECTIONS AS A SUBSTITUTE.ALSO, FBC
 2306, 2307, 2308 AND 2309 MAY ONLY BE
 USED IN AREAS WHERE THE WIND SPEED IS
 100 MPH OR LESS.WEST PALM BEACH IS IN
 AN 140 MPH ZONE.PLEASE REVISE
 ACCORDINGLY AND ENSURE COMPLIANCE WITH
 THE DESIGN STANDARDS CITED IN FBC
 2301.2.5.
  
 THE COMPONENT AND CLADDING PRESSURES ARE
 NOT DEFINED FOR ALL OF THE ELEMENTS
 EFFECTED.
  
 SHEET 6 OF 6, HOW WAS THE 1.8 INTERNAL
 PRESSURE DETERMINED?
  
 NOTE 8 ROOF NOTES ON SHEET 6 OF 6 CALLS
 OUT ZONES "C & SE" WHERE ON THE PLANS
 ARE THEY DEFINED?
  
 PROVIDE THE REINFORCED MASONRY DESIGN
 CRITERIA CONTAINED IN ACI 530, SEE FBC
 2103.1.
  
 SHEETS A AND B DETAILS DO NOT READILY
 RELATE TO THE PLANS SHEETS 1 THROUGH 6.