Plan Review Notes
Plan Review Notes For Permit 02050779
Permit Number 02050779
Review Stop R
Sequence Number 3
Notes
Date Text
2002-08-08 00:00:00THE STRUCTURAL CALCULATIONS
 ARE NOT NEARLY COMPLETE AND DO NOT
 ADDRESS THE LOADS FROM THE ROOF
 DIAPHRAGM AS REQUESTED.
  
 THE LETTER AND CLACULATIONS PREPARED BY
 C.T. TARNOWSKI, PE ARE NOT SIGNED AND
 SEALED IN ACCORDANCE WITH FBC 104.2.2.
  
 THE TARNOWSKI CALCULATIONS STATE THE
 DESIGN IS TO FBC 1606.2.ONE PAGE
 INVESTIGATES THE WIND MOMENT ON A
 SINGLE FILLED CELL FOR THE 8' WALL
 HEIGHT, BUT IS ABSENT THE CONTRIBUTION
 FROM THE ROOF.SEE FBC 1606.2.4 FOR
 THE MWFRS.
  
 SEE ALSO, FBC 1606.2.2.2 WITH REGARDS
 TO THE ROOF TRUSSES.
  
 THE MASONRY COLUMN SCHEDULE ATTACHED TO
 THE CALCULATIONS, IS THIS INTENDED TO BE
 APPLIED TO THE SHEAR WALLS?
  
 PLEASE PROVIDE CALCULATIONS FOR AT
 LEAST THE FRONT OF THE HOUSE, INCLUDE
 THE CONNECTIONS TO BE USED.SEE FBC
 2310.1.3.
  
 THE SHEET TITLED "MASONRY WALL BOND
 BEAM ANALYSIS".PLEASE DECLARE WHAT
 THE PRESSURES ARE AND WHETHER THEY ARE
 MWFRS OR C&C.
  
 SHEET S1 STILL CALLS OUT A CAST CRETE
 8F22-1B FOR LINTEL "L17" THAT IS NOT
 DESCRIBED IN THE TABLES ON SHEET S2.IF
 THIS IS A SPECIALTY DESIGN PROVIDE A
 CONSTRUCTION DETAIL.
  
 SHEET S2 SHOWS A PARTIALLY BLOCKED ROOF
 DIAPHRAGM AT THE CENTER FRONT OF THE
 HOUSE.HOW AND WHAT MAGNITUDE OF FORCE
 IS CARRIED TO THE SIDEWALLS? (BOUNDARY)
 SEE FBC 2310.2.ALSO, DIAPHRAGM
 SCHEDULE CALLS OUT 8D NAILS AND 19/32
 RATED SHEATHING.FBC TABLE 2310.2A HAS
 VALUES FOR 8D AND 15/32 SHEATHING. THE
 19/32 SHEATHING IS LISTED THEREIN WITH
 10D NAILS.WHAT WAS USED IN THIS
 DESIGN?
  
 SECTION 1/A3 DOES NOT APPEAR TO AGREE
 WITH PLAN VIEW ON SHEET A/1.PLEASE
 CLARIFY.
  
 THE SOFFIT VENT CALCULATIONS ON SHEET
 A-2 SEEMS TO BE MISSING SOMETHING IN
 THE EQUATION.
  
 SECTION 4/A4 AS TAKEN FROM SHEET A-2,
 IMPLIES A MASONRY RAKE WALL TO THE
 GABLED ROOF.THIS DOES NOT AGREE WITH
 THE FOUNDATION PLAN ON S1.
  
 MIAMI DADE NOA 01-0226.04 HAS ONLY THE
 FIRST PAGE AND THEN OTHER PAGES NOT
 PERTINENT TO IT.
  
 NOA 01-0209.11 HAS AN ILLEGIBLE DRAWING.
  
 NOA 01-0209.10 HAS AN ILLEGIBLE DRAWING.
  
 NOA 00-0614.06 HAS AN ILLEGIBLE DRAWING.