2002-06-17 00:00:00 | SHEET S1 DECLARES A DESIGN BASED ON |
| RATIONAL ANALYSIS.PLEASE PROVIDE |
| COMPLETE CALCULATIONS, INCLUDING SOURCE |
| OF REFERENCE(S) FOR WIND LOADS, AS |
| PROVIDED FOR IN ASCE 7-98 SECTION |
| 6.5.8.3.DEMONSTRATE WHAT GUST FACTORS |
| WERE USED AND IN WHAT COMBINATIONS. |
| SHOW THE LOAD PER FOOT TRANSFERRED TO |
| THE MASONRY WALLS BY THE ROOF DIAPHRAGM. |
| |
| SHOW THE MASONRY SPECIFICATION CRITERIA |
| CONTAINED IN ACI 530 1.2.1, |
| PARTICULARLYLENGTHS OF VERTICAL STEEL |
| EMBED IN THE |
| SINGLEBOND BEAMS, GROUT, POUR HEIGHT, |
| CLEAR GROUT SPACE DIMENSION, ETC. |
| |
| S2 WRONGLY CITES ASCE 7-93 AND 110 MPH. |
| THE 2001 FBC INVOKES ASCE 7-98 AND WEST |
| PALM BEACH IS IN THE 140 MPH WIND ZONE. |
| PLEASE REVISE ACCORDINGLY AND NOTE IN |
| ABOVE REQUESTED CALCULATIONS. |
| |
| THE LINTEL SCHEDULE ON SHEET S1 CALLS |
| OUT AN 8F22-1B THAT IS NOT FOUND IN THE |
| JCAST CRETE SCHEDULE, PLEASE CLARIFY |
| THE INTENT. |
| |
| SBCCI REPORT #9933 FOR THE ENTEGRA ROOF |
| TILE IS RATED FOR A 110 MPH WIND ZONE. |
| SEE TABLE 1606.1.6.1 EQUIVALENT BASIC |
| WIND SPEEDS. |
| |
| THE METRO-DADE NOA #01-0209.10 "DESIGNER |
| WINDOWS" HAS AN ILLEGIBLE DRAWING. |
| |
| WHAT IS THE DRAWING LABELED BINNINGS PAN |
| AMERICAN PA 7 11 01 464 INTENDED TO BE |
| USED FOR? |
| |
| NOA 99-0223.04 FOR THE LAWSON MULLIONS, |
| IS EXPIRED. |
| |
| THE ROBICO SHUTTERS, 00-0307.04, DRAWING |
| IS ILLEGIBLE AND THE COMPONENTS ARE NOT |
| SELECTED. |