Plan Review Notes
Plan Review Notes For Permit 02050779
Permit Number 02050779
Review Stop R
Sequence Number 1
Notes
Date Text
2002-06-17 00:00:00SHEET S1 DECLARES A DESIGN BASED ON
 RATIONAL ANALYSIS.PLEASE PROVIDE
 COMPLETE CALCULATIONS, INCLUDING SOURCE
 OF REFERENCE(S) FOR WIND LOADS, AS
 PROVIDED FOR IN ASCE 7-98 SECTION
 6.5.8.3.DEMONSTRATE WHAT GUST FACTORS
 WERE USED AND IN WHAT COMBINATIONS.
 SHOW THE LOAD PER FOOT TRANSFERRED TO
 THE MASONRY WALLS BY THE ROOF DIAPHRAGM.
  
 SHOW THE MASONRY SPECIFICATION CRITERIA
 CONTAINED IN ACI 530 1.2.1,
 PARTICULARLYLENGTHS OF VERTICAL STEEL
 EMBED IN THE
 SINGLEBOND BEAMS, GROUT, POUR HEIGHT,
 CLEAR GROUT SPACE DIMENSION, ETC.
  
 S2 WRONGLY CITES ASCE 7-93 AND 110 MPH.
 THE 2001 FBC INVOKES ASCE 7-98 AND WEST
 PALM BEACH IS IN THE 140 MPH WIND ZONE.
 PLEASE REVISE ACCORDINGLY AND NOTE IN
 ABOVE REQUESTED CALCULATIONS.
  
 THE LINTEL SCHEDULE ON SHEET S1 CALLS
 OUT AN 8F22-1B THAT IS NOT FOUND IN THE
 JCAST CRETE SCHEDULE, PLEASE CLARIFY
 THE INTENT.
  
 SBCCI REPORT #9933 FOR THE ENTEGRA ROOF
 TILE IS RATED FOR A 110 MPH WIND ZONE.
 SEE TABLE 1606.1.6.1 EQUIVALENT BASIC
 WIND SPEEDS.
  
 THE METRO-DADE NOA #01-0209.10 "DESIGNER
 WINDOWS" HAS AN ILLEGIBLE DRAWING.
  
 WHAT IS THE DRAWING LABELED BINNINGS PAN
 AMERICAN PA 7 11 01 464 INTENDED TO BE
 USED FOR?
  
 NOA 99-0223.04 FOR THE LAWSON MULLIONS,
 IS EXPIRED.
  
 THE ROBICO SHUTTERS, 00-0307.04, DRAWING
 IS ILLEGIBLE AND THE COMPONENTS ARE NOT
 SELECTED.