Plan Review Notes
Plan Review Notes For Permit 02050775
Permit Number 02050775
Review Stop R
Sequence Number 3
Notes
Date Text
2002-08-14 00:00:00BUILDING REVIEW APPROVED WITH PROVISO-
 (AS PER MEETING W/ CONTRACTOR, ARCHITECT
 AND PLAN REVIEWERS. 8-14-02):
 1-PROVIDE ENGINEER'GANALYSIS-CALCS
 FOR CLARIFICATION OF HOW THE MAIN WIND
 FORCE RESISTING SYSTEM (MWFRS) WAS
 DESIGNED TO RESIST AND TRANSFER ALL
 LOADS TO FLOOR AND CEILING DIAPHRAGMS
 CONSIDERING THE DOUBLE CEILING AREAS
 AND PARTIAL FLOOR DIAPHRAGM. SEE SEC.
 1606.2.4 FBC 2001.
 **PROVIDE ENGINEERING ANALYSIS/CALCS FOR
 CLARIFICATION OF MASONRY WALLS LATERAL
 STABILITY (SEC. 2105 FBC) AND LATERAL
 SUPPORT (SEC. 2107 FBC) CONSIDERING
 THE HIGH VOLUME AREA SHOWN ON PLANS.
 2-NEED FIREBLOCKING @ TOP OF STAIRS TOO.
 SEC. 2305.1.4 FBC. SPECIFY MATERIAL &
 SIZE.
 3-PROVIDE SOIL TEST REPORT.
 4-PROVIDE COMPLETE INFORMATION WITH
 UPDATED PRODUCT APPROVAL FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT,
 SINCE COMPLETE/RIGHT INFORMATION WAS
 NOT SUBMITTED WITH PLANS. SEE CITY
 IMPLEMENTATION STANDARD FOR HURRICANE
 MISSILE IMPACT PROTECTION.
 5-PROVIDE LEGIBLE PRODUCT APPROVAL FOR
 DOORS, WINDOWS AND MULLIONS TO BE USED
 **NOTE: SEE ARCHITECTURAL PLANS FOR
 RIGHT SIZE, SHAPE AND DESIGN PRESSURES
 **ALSO, VERIFY THAT DRAWINGS IN PRODUCT
 APPROVAL MATCH THEIR REPORTS.
 6-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 ARCHED WINDOWS AS REQUIRED BY THE
 PRODUCT APPROVAL.
 **NOTE: NEED DETAIL FOR FRAMED ARCH AND
 FOR MASONRY ATTACHMENT.
 7-NOTE 2 SHEET A-1: PROVIDE DETAIL THAT
 SHOWS WINDOW RECESSED 4.5" FOR THE
 INSTALLATION OF STORM SHUTTERS.
 **NOTE: SEE PRODUCT APPROVAL FOR
 TRACK USED AND CONSIDER THE GLASS
 SEPARATION AND EDGE DISTANCE.
 8-SEE PRODUCT APPROVAL FOR GARAGE DOORS
 FOR STRUCTURAL BUCK SPECS AND REVISE
 DETAIL AS REQUIRED.
 9--SPECIFY FIREBLOCKING IN WALL SECTIONS
 AND PROVIDE GENERAL SPECIFICATIONS FOR
 REQUIRED FIREBLOCKING AT ALL CONCEALED
 SPACES. SEC. 2305.1.4
 10-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL DETAILS AS WELL.
 SEC. 2305.4 FBC.
 11-STAIR FLOOR PLAN: CLARIFY NOTE #13.
 REVISE STAIR DETAILS. REMEMBER THAT
 WOOD COLUMN WILL BE CHANGED FOR STEEL
 COLUMN. ALSO, VERIFY THAT KEY NOTES
 FOR STAIRS MATCH STAIR DETAILS.
 CLARIFY/REVISE STAIR RATIO CALCS.
 12-SPECIFY SPACING FOR WWM SUPPORTS. SEE
 SEC. 1909.3 FBC 2001.
 13-SHEET S-1: SOME DETAILS AND NOTES ARE
 OVERLAPPING OR DETAILS NOT SHOWN.
 CLARIFY/REVISE ASSIGNED DETAIL NUMBER
 AND SHEET # ASSIGNED FOR THE PRIVACY
 WALLS.
 14-SHEET S-2: UPDATE NOTE #2. SEMCO IS
 OUT OF BUSINESS. UPDATE AS REQUIRED.
 15-SHEET S-3: IDENTIFY ROOF ZONE 3 FOR
 NAILING DIAPHRAGM.
 **NOTE: ZONE 3 DOESN'T REFER TO GABLE
 ENDS ONLY. ALL CORNER ARE INCLUDED TOO
 **REVISE TRUSS CONNECTOR SCHEDULE:
 NUMBER OF FASTENERS SPECIFIED AND
 ALLOWABLE UPLIFT DON'T MATCH. SEE USP
 CATALOGUE. PROVIDE ENGINEERED CALCS
 FOR UPLIFT LOADS DIFFERENT THAN THOSE
 SPECIFIED ON CATALOGUE.
 16-PROVIDE ATTIC ACCESS ABOVE GARAGE AND
 MORNING ROOMIF CLEAR HEIGHT IS MORE
 THAN 24". SEC. 2309.6 FBC 2001.
 17-IF PROVIDING MASONRY LETTER, THEN IT
 NEEDS TO BE UPDATED & ADDRESSED TO THE
 CITY OF WPB & CONTRACTOR AND IDENTIFY
 SPECIFIC PROJECT.