Plan Review Notes For Permit 02050775 |
Permit Number |
02050775 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-04 00:00:00 | *******************DENIED*************** | | | | MECHANICAL PERMIT 02050801 | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | SMOKE DETECTORS SHALL BE INSTALLED IN | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | AIR DUCT. 2001 FBC(M) 606.2.1 | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | WITH NOTIFICATION TO ALARM/STOBE OR AREA | | SMOKE DETECTORS. 2001 FBC(M) 606.4.1 | | | | PLEASE NOTE PLANS SHEET MP-2 DRAWING - | | SECOND FLOOR MECH & PLUMBING PLAN.HVAC | | DETAIL INDICATES "GROUND FLOOR" INSTEAD | | OF SECOND FLOOR. | | | | DRYER VENT SHALL BE A MINIMUM OF 4". NO | | SIZE INDICATED ON PLAN. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|