2002-06-04 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02050801
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STOBE OR AREA
 SMOKE DETECTORS. 2001 FBC(M) 606.4.1
  
 PLEASE NOTE PLANS SHEET MP-2 DRAWING -
 SECOND FLOOR MECH & PLUMBING PLAN.HVAC
 DETAIL INDICATES "GROUND FLOOR" INSTEAD
 OF SECOND FLOOR.
  
 DRYER VENT SHALL BE A MINIMUM OF 4". NO
 SIZE INDICATED ON PLAN.
  