2002-07-30 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SANITARY RISER DIAGRAM NOT TO CODE.
 BATHROOMS FROM 2ND FLOOR SHALL NOT DRAIN
 INTO VENT STACK FOR 1ST FLOOR BATHROOM.
 MOP SINK NOT SHOWN ON RISER DIAGRAM.
 2) FROM PREVIOUS REVIEW: (#4), CLEAR
 FLOOR SPACE NOT SHOWN. LAV CABINET CAN
 NOT INTRUDE INTO 5' TURNING RADIUS. LAV
 SHALL BE 15" OFF WALL TO CENTER OF FIX-
 TURE. (CENTERED IN CLEAR FLOOR SPACE)
 11-4.19.3. HEIGHT FOR LAV 11-4.19.2.
 W/C SHALL BE 1'6" OFF WALL TO CENTER OF
 FIXTURE. SHOW DETAILS FOR SHOWER STALL,
 SEC 11-4.21 AND ALL SUBSECTIONS. SEE
 FIG'S 35 & 37(B). PLEASE SHOW CLEAR DE-
 TAILS FOR ALL FIXTURES IN ACCESSIBLE
 BATHROOM.
 3) WHERE IS BATHROOM FOR BEDROOM #3 IN
 BLDG "B".
 4) SHT A-3 HDCP BATHROOM REQUIREMENTS,
 TOILET HEIGHT SHALL READ 17"-19". LAV
 34" TO LAV/COUNTER TOP.
  
 REVIEW BY KEN STEVENS