Plan Review Notes For Permit 02050736 |
Permit Number |
02050736 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-07-30 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | FBC-2001 FUEL GAS | | | | 1) SANITARY RISER DIAGRAM NOT TO CODE. | | BATHROOMS FROM 2ND FLOOR SHALL NOT DRAIN | | INTO VENT STACK FOR 1ST FLOOR BATHROOM. | | MOP SINK NOT SHOWN ON RISER DIAGRAM. | | 2) FROM PREVIOUS REVIEW: (#4), CLEAR | | FLOOR SPACE NOT SHOWN. LAV CABINET CAN | | NOT INTRUDE INTO 5' TURNING RADIUS. LAV | | SHALL BE 15" OFF WALL TO CENTER OF FIX- | | TURE. (CENTERED IN CLEAR FLOOR SPACE) | | 11-4.19.3. HEIGHT FOR LAV 11-4.19.2. | | W/C SHALL BE 1'6" OFF WALL TO CENTER OF | | FIXTURE. SHOW DETAILS FOR SHOWER STALL, | | SEC 11-4.21 AND ALL SUBSECTIONS. SEE | | FIG'S 35 & 37(B). PLEASE SHOW CLEAR DE- | | TAILS FOR ALL FIXTURES IN ACCESSIBLE | | BATHROOM. | | 3) WHERE IS BATHROOM FOR BEDROOM #3 IN | | BLDG "B". | | 4) SHT A-3 HDCP BATHROOM REQUIREMENTS, | | TOILET HEIGHT SHALL READ 17"-19". LAV | | 34" TO LAV/COUNTER TOP. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|