Date |
Text |
2002-07-29 00:00:00 | A RESIDENTIAL FIRE SPRINKLER SYSTEM, |
| (13R), IS NOT A RECOGNIZED ALTERNATE |
| FOR OTHER CODE REQUIREMENTS.SEE FBC |
| 903.2 AND FBC 903.7.5. |
| |
| THE STAIRS FROM THE SECOND FLOOR IN |
| BLDGA ARE REQUIRED TO BE ENCLOSED IN |
| FIRE RATED CONSTRUCTION AND TO PROVIDE |
| A CONTINUOUS PROTECTED PATH TO THE |
| OUTSIDE.SEE FBC 1006.1 AND FBC |
| 1010.1.1. |
| |
| THE FIRE PROTECTION DESIGN IS REQUIRED |
| TO APPEAR ON THE PERMIT PLANS.SEE FBC |
| 104.1. (SPRINKLER & ALARM) |
| |
| IF TEST NOTICE OF ACCEPTANCE REPORTS ARE |
| NOT INCLUDED WITH THE PERMIT PLANS FOR |
| THE NEW AND OR RELOCATED DOORS AND |
| WINDOWS, A SEPARATE PERMIT AND FEES FOR |
| THAT WORK WILL BE REQUIRED.SEE |
| ATTACHED "IMPLEMENTATION STANDARD"ALSO |
| SHOW HOW HURRICANE MISSILE IMPACT |
| RESISTANCE WILL BE ACCOMPLISHED. |
| |
| SHOW THE COMPONENT AND CLADDING DESIGN |
| PRESSURES FOR THE OPENINGS. |
| |
| THE RG THOMAS LETTER DATED JULY 8, 2002, |
| IN ITEM #3 DECLARES THAT THE SOUTH |
| BUILDING WOULD NOT HAVE PUBLIC AREAS |
| AND THEREFORE NEED NOT BE ACCESSIBLE. |
| THE PLANS SHOW THREE BEDROOM SUITES AND |
| A MANAGER'S APARTMENT.WILL THE SUITES |
| NOT BE AVAILABLE TO THE PUBLIC? |
| |
| PROVIDE DETAILS FOR THE FISH POND SHOWN |
| ON SHEET SP 1. |
| |
| SHOW THE FIRE RATED TENANT SEPARATION |
| FOR THE SUITES IN ACCORDANCE WITH FBC |
| 704.3. |
| |
| PROVIDE A CONSTRUCTION DETAIL FOR THE |
| EXISTING PATIO TO BE ENCLOSED AT THE |
| REAR OF BUILDING A, AND FOR THE FRONT |
| PORCH AS WELL. |
| |
| AN 8.5 X 11 SHEET INCLUDED WITH THE |
| PERMIT SUBMITTAL SHOWS TWO PARKING |
| SPACES OFF THE ALLEY AT THE REAR OF |
| BUILDING A.SHOW THE REQUIRED HC SPACE |
| ON AN ACCESSIBLE ROUTE. |
| |
| SHOW THE SIGNAGE FOR THE HC ACCESSIBLE |
| ENTRANCE WHICH WILL NOT BE AT THE MAIN |
| PUBLIC ENTRANCE. SEE FBC 11-4.1.2 (7). |
| |
| SHEET A1, DECLARE THE INTENDED OCCUPANCY |
| USE OF THE ROOMS ON THE FIRST FLOOR OF |
| BLDG A SHOWN ON THE EAST AND WEST SIDES, |
| AND ON THE SECOND FLOOR, THE ROOM IN |
| THE SOUTH WEST CORNER. |
| |
| SHEET A2, BLDG B.WHAT WILL BE THE USE |
| OF THE SECOND FLOOR?HOW WILL EGRESS |
| AND ACCESS BE ACCOMPLISHED SUBSEQUENT |
| TO THE DEMOLILTION OF THE STAIRS?SEE |
| FBC 104.2. |
| |
| SHEET A2, WHERE ARE THE TOILET |
| FACILITIES FOR BEDROOM SUITE #3?SEE |
| FBC 1204. |
| |
| SHEET A2, THE NEW DOOR AT THE FRONT OF |
| THE BUILDING IS NOT PERMITTED TO OPEN |
| DIRECTLY ONTO A FLIGHT OF STAIRS.SEE |
| FBC 1012.1.4. |
| |
| WHAT IS THE CONDITION OF THE DOOR SHOWN |
| AS EXISTING FROM THE MANAGER'S ROOM, |
| GIVEN THAT STAIRS ARE INDICATED ON THE |
| FRONT AND REAR OF THE BUILDING? |
| |
| WHAT WILL THE PORCH INTENDED TO BE |
| ENCLOSED BE USED FOR? |
| |
| SHEET SP1, WHAT DO THE CROSS HATCHED |
| AREAS SHOWN EXTERIOR TO BOTH BUILDINGS |
| INDICATE? |
| |
| SHEET A3, SECTION 1A3. A GUARDRAIL AS |
| WELL AS HANDRAILS ARE REQUIRED FOR THE |
| DECK.WHAT IS THE RISE AND RUN OF THE |
| STAIRS?CONSTRUCTION DETAIL? |
| |
| AS PREVIOUSLY NOTED IMPACT FEES MUST BE |
| PAID TO THE COUNTY BEFORE A PERMIT MAY |
| BE ISSUED. |