Date |
Text |
2002-05-23 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 11 |
| |
| 1) PLEASE PROVIDE A SANITARY RISER DIA- |
| GRAM FOR ALL PIPING PROPOSED FOR BATH |
| ROOMS. |
| 2) APPLICATION SAYS REMODEL EXISTING |
| EXISTING BATHROOMS 1ST FLOOR, ADD POWDER |
| ROOM, REMODEL 2ND FLOOR BATHROOM, AND |
| ADD 2 NEW BATHROOMS ON 2ND FLOOR, BUT |
| SAYS NOTHING OF WORK BEING DONE IN A |
| COTTAGE. PLEASE SUPPLY A PLOT PLAN SHOW- |
| ING ALL BLDGS ON PROPERTY. |
| 3) SEPARATE GAS PERMIT REQUIRED FOR GAS |
| WORK BEING DONE. PLEASE SUBMIT INFORMAT- |
| ION REQUIRED FOR GAS PERMIT AS FOLLOWS: |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| FBC-2001 FUEL GAS CODE. |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE. |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE. |
| G. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE. IF NATURAL |
| GAS SPECIFY .5 PSI OR 2 PSI. |
| H. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| I. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| 4) HC BATH #6 PLEASE SHOW DETAILS FOR |
| HDCP BATH. SHOW CLEAR FLOOR SPACE FOR |
| ALL FIXTURES. LAV TO BE 15" OFF THE WALL |
| CENTERED IN CLEAR FLOOR SPACE 11-4.19.3, |
| HEIGHT FOR LAV 4.19.2. W/C SHALL BE 1'6" |
| TO CENTER OFF WALL, HEIGHT 4.16.3, DOOR |
| SHALL NOT SWING INTO CLEAR FLOOR SPACE |
| REQUIRED FOR ANY FIXTURE, 4.22.2, SHOWER |
| STALLS 4.21 AND ALL SUBSECTIONS. PLEASE |
| SHOW CLEAR DETAILS FOR ALL FIXTURES IN |
| HDCP BATHROOM. |
| 5) PLEASE INDICATE ROOM SIZE FOR ALL |
| BATHROOMS. |
| 6) ALL DEMO WORK SHALL BE LEFT EXPOSED |
| FOR INSPECTION PRIOR TO COVERING. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |