Plan Review Notes
Plan Review Notes For Permit 02050736
Permit Number 02050736
Review Stop P
Sequence Number 1
Notes
Date Text
2002-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM FOR ALL PIPING PROPOSED FOR BATH
 ROOMS.
 2) APPLICATION SAYS REMODEL EXISTING
 EXISTING BATHROOMS 1ST FLOOR, ADD POWDER
 ROOM, REMODEL 2ND FLOOR BATHROOM, AND
 ADD 2 NEW BATHROOMS ON 2ND FLOOR, BUT
 SAYS NOTHING OF WORK BEING DONE IN A
 COTTAGE. PLEASE SUPPLY A PLOT PLAN SHOW-
 ING ALL BLDGS ON PROPERTY.
 3) SEPARATE GAS PERMIT REQUIRED FOR GAS
 WORK BEING DONE. PLEASE SUBMIT INFORMAT-
 ION REQUIRED FOR GAS PERMIT AS FOLLOWS:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 FBC-2001 FUEL GAS CODE.
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE.
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE. IF NATURAL
 GAS SPECIFY .5 PSI OR 2 PSI.
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 4) HC BATH #6 PLEASE SHOW DETAILS FOR
 HDCP BATH. SHOW CLEAR FLOOR SPACE FOR
 ALL FIXTURES. LAV TO BE 15" OFF THE WALL
 CENTERED IN CLEAR FLOOR SPACE 11-4.19.3,
 HEIGHT FOR LAV 4.19.2. W/C SHALL BE 1'6"
 TO CENTER OFF WALL, HEIGHT 4.16.3, DOOR
 SHALL NOT SWING INTO CLEAR FLOOR SPACE
 REQUIRED FOR ANY FIXTURE, 4.22.2, SHOWER
 STALLS 4.21 AND ALL SUBSECTIONS. PLEASE
 SHOW CLEAR DETAILS FOR ALL FIXTURES IN
 HDCP BATHROOM.
 5) PLEASE INDICATE ROOM SIZE FOR ALL
 BATHROOMS.
 6) ALL DEMO WORK SHALL BE LEFT EXPOSED
 FOR INSPECTION PRIOR TO COVERING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377