Plan Review Notes
Plan Review Notes For Permit 02050713
Permit Number 02050713
Review Stop R
Sequence Number 1
Notes
Date Text
2002-06-06 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE SKYLIGHTS ON THE LOWER ROOF ARE
 NOT ALLOWED WITHIN 4 FEET OF THE FIRE
 SEPARATION DIVIDING WALL BETWEEN UNITS
 WHERE THE FIRE RETARDENT TREATED WOOD IS
 REQUIRED BY FBC SEC.704.4.1.
  
 3) PLEASE CHANGE NOTE #2 ON A1 TO REFER
 TO FLORIDA BUILDING CODE.
  
 4) PLEASE CHANGE NOTE #1 ON S5 UNDER
 SAFE GUARDS TO REFERENCE THE FBC.
  
 5) PLEASE SHOW ON THE PLANS COMPLIANCE
 WITH THE REQUIREMENT FOR HANDRAILS PER
 FBC SEC. 1007.5 AND THE GUARDRAIL
 REQUIREMENTS PER FBC SEC. 1015. PLEASE
 PROVIDE DETAIL OF GUARDRAIL AND HANDRAIL
  
 6) PLEASE INDICATE ON A4 THAT STUCCO
 APPLIED VERTICALLY ON METAL LATHE OVER A
 SOLID BASE IS REQUIRED TO BE 7/8" THICK
 PER FBC SEC.2504.2 AND ASTM C-926.
  
 7) PLEASE CLARIFY HOW THE LOWER ROOF
 TRUSSES WILL BE ATTACHED OR WILL BEAR AT
 THE SECOND FLOOR WALL. SEE DETAIL E ON
 A4.
  
 8) FIREBLOCKING IS REQUIRED BETWEEN THE
 LOWER ROOF AND THE FLOOR/CEILING
 ASSEMBLY AND THE SECOND FLOOR WALL
 ASSEMBLY PER FBC 2305.1.
  
 9) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES FOR THE SKYLIGHTS.
  
 10) PLEASE INDICATE ON THE PLANS THAT
 ADEQUATE SUBSTRATE WILL BE PROVIDED FOR
 THE ATTACHMENT OF THE STORM PANELS AT
 THE WOOD FRAME OPENINGS.
  
 11) SPECIFY ON THE PLANS THE FASTENERS
 AND METHOD OF ATTACHMENT THAT WILL BE
 USED TO CONSTRUCT THE BUILT UP WOOD
 COLUMNS WC2 AND WC3. SEE S3.
  
 12) PLEASE CORRECT DETAIL 1 ON S3 WHICH
 INDICATES 3/16" HOLES FOR THE 3/4" BOLTS
  
 13) PLEASE CORRECT THE FOLLOWING NOTES
 ON S5 :
 - NOTE #5 UNDER SAFEGUARDS REFERS TO
 STANDARD BUILDING CODE
 - NOTE #5 UNDER ROOF SHEATHING REFERS TO
 SBC
 - NOTE #1 REFERS UNDER REINFORCED
 CONCRETE REFERS TO SBC AND NOTE #5
 STATES THAT SOIL IS USED AS A FORM. THE
 CITY AMENDMENTS TO THE FBC SEC. 1804.1.1
 REQUIRES ALL FOOTINGS AND CONCRETE PADS
 TO BE FORMED FULL DEPTH.
 - NOTE #7 REFERS TO ASTM 1-185 AND IT
 SHOULD BE ASTM A-185. THE NOTES STATE
 THAT WWF SHOULD BE LIFTED DURING
 CONCRETE PLACEMENT, THE FBC SEC. 1909.3
 REQUIRES WIRE FABRIC TO BE SUPPORTED.
  
 14)PLEASE CORRECT THE DESIGN INFORMATION
 GIVEN ON S1. THE EXPOSURE CATAGORY IS B,
 THE IMPORTANCE FACTOR IS 1.00, THE ASCE
 TABLE IS 6-1 IN ASCE 7-98. PLEASE
 INDICATE THE INTERNAL PRESSURE
 COEFFICIENT (+OR- .18 FOR ENCLOSED).
 THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 15) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THIS MODEL (G). THE ONES
 THAT WERE SUBMITTED ARE FOR MODEL "A".
  
 16) POSITIVE PRESSURE LISTED ON THE PLAN
 FOR THE SH25 WINDOWS IN THE MASTER BED-
 ROOM EXCEED THOSE LISTED IN THE SBCCI
 REPORT. HOWEVER,THE COMPARATIVE ANALYSIS
 CHART PRESSURES EXCEED THOSE REQUIRED ON
 THE PLANS. PLEASE SUBMIT THE ENGINEERS
 CALCULATIONS USED TO ARRIVE AT THESE
 VALUES,SIGNED AND SEALED BY THE ENGINEER
  
 17) PROVIDE CURRENT PRODUCT APPROVALS
 FOR SKYLIGHTS. THE ONES SUBMITTED
 EXPIRED 5-2-02, PRIOR TO SUBMITTAL.
  
 18) PROVIDE PRODUCT APPROVALS FOR FRENCH
 DOOR AS INDICATED ON PLANS AT ENTRY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202