Plan Review Notes For Permit 02050713 |
Permit Number |
02050713 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-03 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | PROTECTION ON PANEL SCHEDULE PER 210-12 | | | | 2)NOTE: PLEASE NOTE OCP FOR 10KW AHU | | PER 424-3B MIN 125%. | | | | 3)NOTE: PLEASE SEE 250-66 FOR SIZING | | OF GROUNDING ELECTRODE CONDUCTOR. | | | | 4)NOTE: PLEASE NOTE WASHER SHOWN AS | | 3000W ON LOAD CALCULATIONS AND ON A 20A | | CIRCUIT ON PANEL SCHEDULE?? | | PLEASE VERFIY. | | | | 5)NOTE: PLEASE NOTE THE OVEN THAT IS | | SHOWN ON PANEL SCHEDULE IS NOT SHOWN | | IN LOAD CALCULATIONS..?? | | | | 6)NOTE: PLEASE NOTE MISSING OUTLET PER | | 210-52 BEDROOM #2. | | | | 7)NOTE: PLEASE SEE 210-52D FOR PLACEMENT | | OF MASTER BATHROOM RECEPT.(S) | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|