Plan Review Notes For Permit 02050678 |
Permit Number |
02050678 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-04 00:00:00 | *******************DENIED*************** | | | | MECHANICAL PERMIT 02050688 | | | | PLAN SHEET MP-1 LIVING AREA INDICATES | | 2200 CFM.PLEASE CORRECT. | | | | PLAN SHEET MP-2 TWO FAN SCHDULES ON | | PLAN (ONE SHOULD BE FOR A/C EQUIPMENT | | SCHEDULE) AHU LISTED IS A 5 TON SYSTEM. | | PLANS INDICATE A 4 TON SYSTEM.PLEASE | | CORRELATE. | | | | PROVIDE OVERFLOW PROTECTION AS PER 2001 | | FBC(M) 307.2.4. | | | | SMOKE DETECTORS SHALL BE INSTALLED IN | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | AIR DUCT. 2001 FBC(M) 606.2.1 | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | WITH NOTIFICATION TO ALARM/STOBE OR AREA | | SMOKE DETECTORS. 2001 FBC(M) 606.4.1 | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | PLEASE NOTE PROGRAMMABLE THERMOSAT | | REQUIRED AS PER ENERGY CALCS, HVAC | | CREDITS. | | | | DRYER VENT SHALL NOT EXCEED 25' AS PER | | 2001 FBC(M) 504.6. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|