Plan Review Notes For Permit 02050678
Permit Number 02050678
Review Stop M
Sequence Number 1
Notes
Date Text
2002-06-04 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02050688
  
 PLAN SHEET MP-1 LIVING AREA INDICATES
 2200 CFM.PLEASE CORRECT.
  
 PLAN SHEET MP-2 TWO FAN SCHDULES ON
 PLAN (ONE SHOULD BE FOR A/C EQUIPMENT
 SCHEDULE) AHU LISTED IS A 5 TON SYSTEM.
 PLANS INDICATE A 4 TON SYSTEM.PLEASE
 CORRELATE.
  
 PROVIDE OVERFLOW PROTECTION AS PER 2001
 FBC(M) 307.2.4.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STOBE OR AREA
 SMOKE DETECTORS. 2001 FBC(M) 606.4.1
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 PLEASE NOTE PROGRAMMABLE THERMOSAT
 REQUIRED AS PER ENERGY CALCS, HVAC
 CREDITS.
  
 DRYER VENT SHALL NOT EXCEED 25' AS PER
 2001 FBC(M) 504.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.