Plan Review Notes For Permit 02050662 |
Permit Number |
02050662 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-19 00:00:00 | 1) EMERGENCY LIGHTING REQUIRED IN | | INTERIOR STAIRWELL. | | | | 2) PROVIDE SEPARATE PLANS AND PERMITS | | FOR ANY FIRE ALARM SYSTEM REMODEL. | | | | 3) EXITS DO NOT MEET THE 1/2 DIAGONAL | | RULE FOR EXITING WITHOUT FIRE | | SPRINKLERS. | | | | 4) CLASSROOM # 2 DOES NOT HAVE A DOOR | | LEADING DIRECTLY TO THE EXTERIOR. NO | | WINDOWS USED FOR RESCUE ARE SHOWN. | | | | 5) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|