2002-05-30 00:00:00THE CHANGE FROM RESIDENTIAL TO
 EDUCATIONAL IS SUBJECT TO IMPACT FEES
 COLLECTED BY PALM BEACH COUNTY,
 TOGETHER WITH THE ADDED FLOOR AREA AND
 CONVERSION OF THE GARAGE.THE PERMIT
 PLANS MUST BE STAMPED BY THAT OFFICE
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION.CALL
 561-233-5025 FOR MORE INFORMATION.
  
 PROVIDE AN ANALYSIS BY FLORIDA
 REGISTERED ENGINEER AS TO THE ADEQUACY
 OF THE EXISTING SECOND FLOOR STRUCTURE
 TO MEET THE MINIMUM FLOOR LIVE LOADS
 FOR THIS OCCUPANCY INCLUDING THE
 BALCONIES.FBC 106.4.1.
  
 THE SECOND FLOOR EXITS AS SHOWN DO NOT
 COMPLY WITH FBC 1004.1.4, THE 1/2
 DIAGONAL DISTANCE SEPARATION.
  
 PROVIDE DETAILS DEMONSTRATING THE
 "EXISTING EXTERIOR METAL STAIR" MEETS
 THE REQUIREMENTS OF FBC 1006.2 AND FBC
 1021.2.3. INCLUDE THE REQUIREMENTS OF
 FBC 1010.
  
 PROVIDE AN ELEVATOR IN ACCORDANCE WITH
 FBC 11-4.1.3(5)
  
 SHOW THE EMERGENCY EGRESS FOR CLASSROOM
 #2 AS REQUIRED BY FBC 1005.4.2.
  
 SPECIFY THE INFORMATION FOR THE
 DELEGATED ENGINEERING DESIGN FOR THE
 FLOOR TRUSSES, INCLUDING MINIMUM LOADS.
  
 SHOW THE FIRE DESIGN NUMBER FOR THE
 COLUMN PROTECTON SHOWN AS 02 ON SHEET
 S1.ALSO, CLARIFY THE THICKNESS OF THE
 COLUMN0.188"OR 1/4".
  
 SHOW HOW THE DOOR SHOWN AS 1 ON SHEET S1
 WILL COMPLY WITH THE HURRICANE MISSILE
 IMPACT REQUIREMENTS OF FBC 1606.1.4.IF
 TEST REPORTS AND OR PRODUCT NOTICE OF
 ACCEPTANCE ARE NOT INCLUDED WITH THIS
 PERMIT APPLICATION, A SEPARATE PERMIT
 AND FEES WILL BE REQUIRED.SEE ALSO
 THE NOTEABOVE RE: EXTERIOR STAIRS FOR
 FIRE RATINGS.
  
 SPECIFY THE EMBEDMENT DEPTH FOR THE 5/8"
 RED HEADS CALLED OUT ON SHEET S1.