Date |
Text |
2002-05-30 00:00:00 | THE CHANGE FROM RESIDENTIAL TO |
| EDUCATIONAL IS SUBJECT TO IMPACT FEES |
| COLLECTED BY PALM BEACH COUNTY, |
| TOGETHER WITH THE ADDED FLOOR AREA AND |
| CONVERSION OF THE GARAGE.THE PERMIT |
| PLANS MUST BE STAMPED BY THAT OFFICE |
| AND A COPY OF THE PAID RECEIPT ATTACHED |
| TO THE PERMIT APPLICATION.CALL |
| 561-233-5025 FOR MORE INFORMATION. |
| |
| PROVIDE AN ANALYSIS BY FLORIDA |
| REGISTERED ENGINEER AS TO THE ADEQUACY |
| OF THE EXISTING SECOND FLOOR STRUCTURE |
| TO MEET THE MINIMUM FLOOR LIVE LOADS |
| FOR THIS OCCUPANCY INCLUDING THE |
| BALCONIES.FBC 106.4.1. |
| |
| THE SECOND FLOOR EXITS AS SHOWN DO NOT |
| COMPLY WITH FBC 1004.1.4, THE 1/2 |
| DIAGONAL DISTANCE SEPARATION. |
| |
| PROVIDE DETAILS DEMONSTRATING THE |
| "EXISTING EXTERIOR METAL STAIR" MEETS |
| THE REQUIREMENTS OF FBC 1006.2 AND FBC |
| 1021.2.3. INCLUDE THE REQUIREMENTS OF |
| FBC 1010. |
| |
| PROVIDE AN ELEVATOR IN ACCORDANCE WITH |
| FBC 11-4.1.3(5) |
| |
| SHOW THE EMERGENCY EGRESS FOR CLASSROOM |
| #2 AS REQUIRED BY FBC 1005.4.2. |
| |
| SPECIFY THE INFORMATION FOR THE |
| DELEGATED ENGINEERING DESIGN FOR THE |
| FLOOR TRUSSES, INCLUDING MINIMUM LOADS. |
| |
| SHOW THE FIRE DESIGN NUMBER FOR THE |
| COLUMN PROTECTON SHOWN AS 02 ON SHEET |
| S1.ALSO, CLARIFY THE THICKNESS OF THE |
| COLUMN0.188"OR 1/4". |
| |
| SHOW HOW THE DOOR SHOWN AS 1 ON SHEET S1 |
| WILL COMPLY WITH THE HURRICANE MISSILE |
| IMPACT REQUIREMENTS OF FBC 1606.1.4.IF |
| TEST REPORTS AND OR PRODUCT NOTICE OF |
| ACCEPTANCE ARE NOT INCLUDED WITH THIS |
| PERMIT APPLICATION, A SEPARATE PERMIT |
| AND FEES WILL BE REQUIRED.SEE ALSO |
| THE NOTEABOVE RE: EXTERIOR STAIRS FOR |
| FIRE RATINGS. |
| |
| SPECIFY THE EMBEDMENT DEPTH FOR THE 5/8" |
| RED HEADS CALLED OUT ON SHEET S1. |