Plan Review Notes
Plan Review Notes For Permit 02050635
Permit Number 02050635
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-07-09 00:00:001) FUEL HOSES ARE NOT TO EXCEED 18
 FEET IN LENGTH.
  
 2) APPROPRIATE WARNING SIGNS ARE
 REQUIRED AT THE DISPENSING PUMPS.
  
 3) APPROVED LISTED BREAKAWAY DEVICES
 ARE REQUIRED AT FUEL PUMPS.
  
 4) INSTALLATION TO COMPLY WITH NFPA 30
 AND 30A.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497