Plan Review Notes
Plan Review Notes For Permit 02050610
Permit Number 02050610
Review Stop P
Sequence Number 1
Notes
Date Text
2002-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW.
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS.
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92. AND NSPI-5
 4) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 5) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK IF
 VACUUM LINE. (DETAIL/NOTE/OR SUBMITTAL)
 6) VENT - VENT SHALL BE VENTED TO ATMOS-
 PHERE IN A MANNER THAT THE VENT WILL NOT
 BE BLOCKED BY INFESTATION, DEBRIS BUILD
 UP, OR MICROBIOLOGICAL CONTAMINATION.
 LABLE VENT: "POOL SAFETY DEVICE- DO NOT
 HANDLE. (ADD TO NOTES)
 7) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 8) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 9) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 1O) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 11) ALL SHEETS OF A SIGNED AND SEALED
 SET OF PLANS SHALL BE SIGNED AND SEALED.
 8-1/2" X 11" SHEET WITH TITLE BLOCK NOT
 SEALED AND DATED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377