Plan Review Notes For Permit 02050594 |
Permit Number |
02050594 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-23 00:00:00 | UNSAT | | ~~~~~ | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION AND MAKE NECESSARY CHANGES | | IN THE DRAWINGS.RESUBMIT FOR REVIEW. | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2} INDICATE WHAT CIRCUITS,APPLIANCES, | | EQUIPMENT,OR OTHER LOADS ARE BEING | | SERVED BY THE VA RATINGS USED IN THE | | LOAD CALCULATIONS. | | | | 3} NOTE THAT THERE WAS NO WASHER | | INDICATED IN CALC'S. | | | | 4} THERE IS NO DISCONNECTING MEANS OR | | PANEL SHOWN FOR THE SEPERATE BUILDING. | | PLEASE COMPLY WITH ARTICLES 250-31 & 32 | | ALSO 250-32. | | | | 5} THE GUEST HOUSE IS LISTED AS A 60 | | AMP L0AD ON THE PERMIT APPLICATION,BUT | | THE LOAD CALCULATION SHOWS 61.6 | | AMPS,PLEASE CLARIFY. | | | | 6} THE GROUNDING ELECTRODE CONDUCTORS | | MUST COMPLY WITH ARTICLE 250-66.NOTE | | THE #6 SHOWN AS A GEC FOR 3/0 | | CONDUCTORS IS INCORRECT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT. 8392 |
|