Plan Review Notes
Plan Review Notes For Permit 02050583
Permit Number 02050583
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-14 00:00:00~~~~~~~~~~~~~~~~~~PROVISO!~~~~~~~~~~~~~~
  
  
  
 1} PLEASE NOTE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED PER 210-8-A-6.AND COMPLY
 WITH 210-52(1 THROUGH 5).
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 4} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 5} PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.LIGHT PER
 210-70(A)(3).
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392