2002-05-14 00:00:00 | ~~~~~~~~~~~~~~~~~~~PROVISO!~~~~~~~~~~~~~ | | | | 1} PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG. | | | | 2} PLEASE LIST THE REQ`D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | 3} PLEASE NOTE KITCHEN COUNTER- | | -SPACE RECEPT SPACING SHALL MEET ART; | | 210-52C 1,2,3,4,AND 5. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|