2002-05-29 00:00:00PROVISO
 ~~~~~~~
 PLEASE NOTE THE FOLLOWING AND MAKE ANY
 NECESSARY CHANGES BEFORE CALLING FOR
 INSPECTION.
  
 1} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2',6',12' RULE PER 210-52.
 ESPECIALLY NOTE THE BEDROOM LOCATIONS.
  
 2} SMOKE DETECTORS ON THE PLAN DO NOT
 COMPLY WITH NFPA-72.PLEASE INSTALL
 ACCORDING TO 2-2.1.1.1, 2-2.2.1,AND
 2-5.2.1.2
 AT THE STAIRWELL.
  