Plan Review Notes For Permit 02050542
Permit Number 02050542
Review Stop FS
Sequence Number 1
Notes
Date Text
2002-05-16 00:00:001) PLANS DO NOT INDICATE LOCATION OF
 EXISTING FIRE HYDRANT LOCATIONS OR
 DISTANCES TO THEM.
  
 2) PLANS DO NOT INDICATE LOCATIONS OF
 ANY EXISTING BACKFLOW DEVICES. THE
 EXISTING SYSTEM IS BELIEVED TO NOT
 BE EQUIPPED WITH ANY BACKFLOW DEVICES
 WHICH IS A CITY UTILITY REQUIREMENT.
 PLEASE CONTACT THE CITY UTILITIES
 DEPARTMENT FOR CODE REQUIREMENTS.
  
 3) PLANS DO NOT INDICATE THAT REQUIRED
 PRESSURE TESTING WILL BE CONDUCTED
 ON ANY NEW PIPING. PLEASE NOTE THIS
 ITEM ON THE PLANS.
  
 4) PLANS DO NOT INDICATE ANY SPARE
 FIRE SPRINKLER HEADS.
  
 5) THE FIRE SPRINKLER SYSTEM MUST BE
 SUPERVISED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED BY THE FIRE
 RESCUE DEPARTMENT.
  
 6) SINCE THE EXISTING SYSTEM HAS BEEN
 OUT OF SERVICE FOR A LONG PERIOD OF
 TIME, THE CITY WILL REQUIRE THAT THE
 ENTIRE FIRE SPRINKLER SYSTEM BE
 INSPECTED, TESTED, AND CERTIFIED BY A
 LICENSED FIRE SPRINKLER CONTRACTOR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910