Plan Review Notes For Permit 02050542 |
Permit Number |
02050542 |
|
Review Stop |
FS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-16 00:00:00 | 1) PLANS DO NOT INDICATE LOCATION OF | | EXISTING FIRE HYDRANT LOCATIONS OR | | DISTANCES TO THEM. | | | | 2) PLANS DO NOT INDICATE LOCATIONS OF | | ANY EXISTING BACKFLOW DEVICES. THE | | EXISTING SYSTEM IS BELIEVED TO NOT | | BE EQUIPPED WITH ANY BACKFLOW DEVICES | | WHICH IS A CITY UTILITY REQUIREMENT. | | PLEASE CONTACT THE CITY UTILITIES | | DEPARTMENT FOR CODE REQUIREMENTS. | | | | 3) PLANS DO NOT INDICATE THAT REQUIRED | | PRESSURE TESTING WILL BE CONDUCTED | | ON ANY NEW PIPING. PLEASE NOTE THIS | | ITEM ON THE PLANS. | | | | 4) PLANS DO NOT INDICATE ANY SPARE | | FIRE SPRINKLER HEADS. | | | | 5) THE FIRE SPRINKLER SYSTEM MUST BE | | SUPERVISED BY A LICENSED UL LISTED | | CENTRAL STATION APPROVED BY THE FIRE | | RESCUE DEPARTMENT. | | | | 6) SINCE THE EXISTING SYSTEM HAS BEEN | | OUT OF SERVICE FOR A LONG PERIOD OF | | TIME, THE CITY WILL REQUIRE THAT THE | | ENTIRE FIRE SPRINKLER SYSTEM BE | | INSPECTED, TESTED, AND CERTIFIED BY A | | LICENSED FIRE SPRINKLER CONTRACTOR. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|