2002-06-03 00:00:00DENIED:
  
 1. EXHAUST AIR EQUALS 1000CFM AND
 OUTSIDE AIR EQUALS 240 CFM WHICH HAS
 THIS BUILDING APPARENTLY 760 CFM
 NEGATIVE. PROVIDE INFORMATION ON WHERE
 ADDITIONAL OUTSIDE IS FROM TO AVOID
 NEGATIVE PRESSURE ON BUILDING.
  
 2. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR AHU, WITH NOTIFICATION BY
 BY BUILDING ALARM SYSTEM.
  
 3. NOTE: AHU LOCATION SHALL BE IN
 RESPECT TO BUILDING CONSTRUCTION TO
 ALLOW FOR SERVICE AND REPLACEMENT OF
 EQUIPMENT WITHOUT RESTRICTION OR
 REMOVAL OF BUILDING COMPONENTS.