Plan Review Notes For Permit 02050442 |
Permit Number |
02050442 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-03 00:00:00 | DENIED: | | | | 1. EXHAUST AIR EQUALS 1000CFM AND | | OUTSIDE AIR EQUALS 240 CFM WHICH HAS | | THIS BUILDING APPARENTLY 760 CFM | | NEGATIVE. PROVIDE INFORMATION ON WHERE | | ADDITIONAL OUTSIDE IS FROM TO AVOID | | NEGATIVE PRESSURE ON BUILDING. | | | | 2. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | REQUIRED FOR AHU, WITH NOTIFICATION BY | | BY BUILDING ALARM SYSTEM. | | | | 3. NOTE: AHU LOCATION SHALL BE IN | | RESPECT TO BUILDING CONSTRUCTION TO | | ALLOW FOR SERVICE AND REPLACEMENT OF | | EQUIPMENT WITHOUT RESTRICTION OR | | REMOVAL OF BUILDING COMPONENTS. |
|