Plan Review Notes
Plan Review Notes For Permit 02050441
Permit Number 02050441
Review Stop M
Sequence Number 1
Notes
Date Text
2002-06-03 00:00:00DENIED
  
 1. EXHAUST AIR EQUALS 1000 CFM AND
 OUTSIDE AIR EQUALS 240 CFM WHICH HAS
 THIS BUILDING APPARENTLY 760 CFM
 NEGATIVE. PROVIDE INFORMATION ON WHERE
 ADDITIONAL OUTSIDE AIR IS FROM TO AVOID
 NEGATIVE PRESSURE ON BUILDING.
  
 2. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR AHU, WITH NOTIFICATION BY
 BUILDING ALARM SYSTEM.
  
 3. NOTE: AHU LOCATION SHALL BE IN
 RESPECT TO BUILDING CONSTRUCTION TO
 ALLOW FOR SERVICE AND REPLACEMENT OF
 EQUIPMENT WITHOUT RESTRICTION OR
 REMOVAL OF BUILDING COMPONENTS


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved