Plan Review Notes For Permit 02050434 |
Permit Number |
02050434 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-06-24 00:00:00 | ********* NOTED/REDLINED ************* | | | | PLEASE NOTE PLANS REDLINED FOR SOME | | CORRECTIONS. | | | | PLEASE NOTE PANEL SCHEDULES NEED TO | | CORRELATE OCP/WIRE/LOADS. WATER HEATERS, | | AND SUB-PANEL | | | | MISSING BATH GFI REC DOWNSTAIRS. | | 210-52D/210-8 | | | | NOTED CLOSET LT CLEARENCE REQ`D PER | | 410-8. | | | | PLEASE NOTE THE ABOVE WAS REDLINED AS | | NOTES. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|