Plan Review Notes
Plan Review Notes For Permit 02050431
Permit Number 02050431
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-21 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE CIRCUITS ON RISER
 FOR NEW 9,11,13,15 ARE COMING FROM A
 277/480 PANEL?? RECEPTS? 277V?
 PLEASE CLARIFY.
  
 2 )NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
  
 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 215-2,215-3,230-42
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372