Plan Review Notes
Plan Review Notes For Permit 02050384
Permit Number 02050384
Review Stop M
Sequence Number 1
Notes
Date Text
2002-05-10 00:00:00PROVISO:
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 PRESSURE DIFFERNTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001" WC OR
 LESS. PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH
 PRESSURE ZONE TO THE LOW ZONE.
  
 BALANCING DAMPERS OR OTHER MEANS OF
 SUPPLY AIR ADJESTMENT SHALL BE PROVIDED
 IN THE BRANCH DUCTS OR AT EACH
 INDIVIDUAL DUCT REGISTER, GRILLE OR
 DIFFUSER.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved