2002-06-13 00:00:00 | CHECKLIST: |
| 1-PAY IMPACT FEES. |
| 2-APPLY FOR IRRIGATION UNDER A SEPARATE |
| PERMIT. |
| 3-A)CLARIFY DETAIL @ LEDGER THAT SUPPORT |
| ROOF TRUSSES. CONNECTORS SPECIFIED TO |
| HOLD TRUSS GIRDERS & ALL OTHER TRUSSES |
| ARE TENSION CONNECTORS. DON'T YOU NEED |
| TO USE TRUSS HANGERS TO SUPPORT THE |
| TRUSSES RESTING ON THE 2X LEDGER? |
| B)SEE DRAWING #7 FOR ADDITIONAL COMMENTS |
| COMMENTS. |
| C)REVISE ANCHOR SCHEDULE. UPLIFT LOADS |
| GIVEN DON'T MATCH UPLIFT LOADS SHOWN |
| ON SIMPSON CATALOGUE ACCORDING TO # OF |
| NAILS USED. PROVIDE ENGINEERING CALCS. |
| D)PROVIDE ENGINEERING CALCULATIONS FOR |
| THE 4 CONNECTORS SPECIFIED ON DET. D/7 |
| TAKE INTO CONSIDERATION THE CLOSENESS |
| OF ONE ANOTHER FOR THE EFFECTIVE |
| STRUCTURAL AREA OF EACH CONNECTOR. |
| 4-UPDATE ALL DRAWINGS TO FBC 2001. SEE |
| COMMENTS ON DRAWINGS & RETURN REVIEWED |
| SETS AFTER CORRECTIONS ARE DONE TO THE |
| ORIGINAL DRAWINGS TO EXPEDITE REVIEW. |
| 5-PROVIDE PRODUCT APPROVAL FOR: |
| A)ENTRY DOORS WITH TRANSOM ABOVE SINGLE |
| ASSEMBLY AS SHOWN ON PLANS. |
| B)WINDOW MULLIONS, ARCHED WINDOWS,SINGLE |
| HUNG WINDOWS AND SLIDING GLASS DOORS |
| PACKAGES SUBMITTED ARE NOT ACCEPTABLE. |
| THEY NEED TO BE OFFICIAL PRODUCT |
| APPROVALS OR SITE SPECIFIC WITH ALL |
| THE SPECIFIC CALCULATIONS, FASTENERS, |
| TESTS, ETC. SEE COMMENTS ATTACHED TO |
| THEM. |
| **USE ATTACHED FORM AS A SAMPLE FOR SITE |
| SPECIFIC ADDITIONAL INFORMATION REQ'D. |
| **ALSO, ARCHITECT TO APPROVE ALL SITE |
| SPECIFIC SUBMITTALS. |
| 6-UPDATE CERTIFICATION LETTER FOR TWO HR |
| FIRE RATED CONCRETE BLOCK. REFER TO |
| FBC 2001. PROVIDE ORIGINAL LETTER. |
| 7-STORM SHUTTERS: |
| A)REVISE KEY PLAN AND ANCHOR SCHEDULE TO |
| MATCH PLANS. SEE PLANS. |
| B)CLEARLY INDICATE ON DWGS ANCHOR SCHED. |
| CONNECTOR TYPE AND SPACING TO BE USED |
| ACCORDING TO EDGE DISTANCE, STRUCTURE |
| TO BE ATTACHED TO ETC. |
| |
| NOTES: |
| *THESE COMMENTS APLY TO LOTS 7 & 8. |
| *DRAWINGS AND COMMENTS TO BE FILED UNDER |
| PERMIT #02050254. |