2002-05-09 00:00:00 | PROVISO: | | | | BALANCED RETURN AIR - PRESSURE | | DIFFERENTIALS ACROSS CLOSED DOORS WHERE | | RETURNS ARE CENTRALLY LOCATED SHALL BE | | LIMITED TO .001" WC OR LESS.PROVIDE | | AIR DUCT PATHWAYS OR AIR TRANSFER | | PATHWAYS FROM THE HIGH PRESSURE ZONE TO | | THE LOW ZONE.2001 FBC(M) 601.4. | | | | BALANCING DAMPERS OR OTHER MEANS OF | | SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED | | IN THE BRANCH DUCTS OR AT EACH | | INDIVIDUAL DUCT REGISTER, GRILLE OR | | DIFFUSER.2001 FBC(M) 603.15. | | | | CONDENSATE SHALL DISCHARGE 12" AWAY FROM | | THE BUILDING STRUCTURE AS PER 2001 FBC | | 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|