Plan Review Notes For Permit 02050224 |
Permit Number |
02050224 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-08 00:00:00 | PROVISO: | | | | AS PER 2001 FBC(M) 601.4 BALANCED RETURN | | AIR, PRESSURE DIFFERENTIALS ACROSS | | CLOSED DOORS WHERE RETURNS ARE | | CENTRALLY LOCATED SHALL BE LIMITED TO | | .001" WC.PROVIDE AIR DUCT PATHWAYS OR | | AIR TRANSFER PATHWAYS FROM THE HIGH | | PRESSURE ZONE TO THE LOW ZONE. | | | | BALANCING DAMPERS OR OTHER MEANS OF | | SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED | | IN THE BRANCH DUCTS OR AT EACH | | INDIVIDUAL DUCT REGISTER, GRILLE OR | | DIFFUSER. 2001 FBC(M) 603.15. | | | | DUCTS SHALL NOT BE INSTALLED IN OR | | WITHIN 6" OF THE EARTH. 2001 FBC(M) | | 603.12. | | | | IF YOU HAVE ANY QUESTION, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|