2002-05-08 00:00:00PROVISO:
  
 AS PER 2001 FBC(M) 601.4 BALANCED RETURN
 AIR, PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE
 CENTRALLY LOCATED SHALL BE LIMITED TO
 .001" WC.PROVIDE AIR DUCT PATHWAYS OR
 AIR TRANSFER PATHWAYS FROM THE HIGH
 PRESSURE ZONE TO THE LOW ZONE.
  
 BALANCING DAMPERS OR OTHER MEANS OF
 SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED
 IN THE BRANCH DUCTS OR AT EACH
 INDIVIDUAL DUCT REGISTER, GRILLE OR
 DIFFUSER. 2001 FBC(M) 603.15.
  
 DUCTS SHALL NOT BE INSTALLED IN OR
 WITHIN 6" OF THE EARTH. 2001 FBC(M)
 603.12.
  
 IF YOU HAVE ANY QUESTION, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.