Plan Review Notes For Permit 02050217 |
Permit Number |
02050217 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-29 00:00:00 | PROVISO: | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | PRESSURE DIFFERNTIALS ACROSS CLOSED | | DOORS WHERE RETURNS ARE CENTRALLY | | LOCATED SHALL BE LIMITED TO .001" WC OR | | LESS. PROVIDE AIR DUCT PATHWAYS OR AIR | | TRANSFER PATHWAYS FROM THE HIGH PRESSURE | | ZONE TO THE LOW ZONE. | | | | AS PER 2001 FBC(M) 602.2.1, MATERIALS | | EXPOSED WITHIN PLENUMS SHALL BE NON - | | COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD | | INDEX OF NOT MORE THAN 25 AND SMOKE - | | DEVELOPED INDEX OF NOT MORE THAN 50 WHEN | | TESTED IN ACCORDANCE WITH ASTM E 84. | | | | FIRE DAMPERS (NEW OR EXISTING) ARE NOT | | IDENTIFIED ON PLAN.PLEASE REVISE PLANS | | TO INDICATE LOCATIONS OF ALL FIRE OR | | FIRE/SMOKE DAMPERS.2001 FBC(M) 607.6. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|