Plan Review Notes For Permit 02050142 |
Permit Number |
02050142 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-06 00:00:00 | PROVISO: | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | BALANCED AIR RETURN - PRESSURE | | DIFFERENTIALS ACROSS CLOSED DOORS WHERE | | RETURNS ARE CENTRALLY LOCATED SHALL BE | | LIMITED TO .001" WC OR LESS.PROVIDE | | AIR DUCT PATHWAYS OR AIR TRANSFER | | PATHWAYS FROM THE HIGH PRESSURE ZONE TO | | THE LOW ZONE.2001 FBC(M) 601.4. | | | | BALANCING DAMPERS OR OTHER MEANS OF | | SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED | | IN THE BRANCH DUCTS OR AT EACH | | INDIVIDUAL DUCT REGISTER, GRILLE OR | | DIFFUSER. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|