2002-06-06 00:00:00 | |
| BUILDING PLAN REVIEW |
| PERMIT: 02041953 |
| ADD: LOT#30 SEC#6 RENAISSANCE |
| CONT: HOME DYNAMICS |
| TEL:(954) 520-1698 (MIKE HANLEY) |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)FL BLDG 1909.3 (EXEPTION# 2) |
| CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| PORTED BY APPROVED MATERIALS OR SUPPORTS |
| AT SPACING NOT TO EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURER'S SPEC. |
| |
| 2)1804.1.3 THE BOTTOM OF THE FOUNDA- |
| TION SHALL EXTEND NO LESS THAN 12" |
| BELOW FINISH GRADE. |
| |
| 3) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| THIS REPORT PAGE 9 OF 9 LIMITATIONS, |
| RESTATES THAT NOT SUFFICIENT FOR A FINAL |
| DESIGN OF THE FOUNDATION SYSTEM. |
| |
| 4) SH.A-1 CENTER BOTTOM OF PAGE DISCREP- |
| ANCY, PLANS READ " CONFORM TO 2001 FBC/ |
| ASCE 5-95" SHOULD READ 7-98. |
| |
| 5) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. |
| A) CLOSPAY OVERHEAD GARAGE DOOR; HIGH- |
| LIGHT WHICH MODEL SHALL BE USED FOR |
| PRESSURES DESIGN. |
| B) MISSING REPORT FOR THE FRONT ENTRY |
| DOOR. PROVIDE DADE COUNTY OR SBCCI RE- |
| PORT, (2 COPIES). |
| C) MISSING ROOFING ASSEMBLIES REPORT, |
| DADE COUNTY OR SBCCI ARE ACCEPTED. |
| D) 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| E) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| F)PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. |
| |
| 6)1707.4.4.1 ANCHOR REQUIREMENTS: |
| WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR |
| ED IN ACCORDANCE WITH THE PUBLISHED |
| MANUFACTURER'S RECOMMENDATIONS TO |
| ACHIEVE THEDESIGN PRESSURE SPECIFIED. |
| SUBSTITUTE ANCHORING SYSTEM USED FOR |
| THE SUBSTRATE NOT SPECIFIED BY THE |
| FENESTRATION MANUFACTURER SHALL PROVIDE |
| EQUAL OR GREATER ANCHORING AS DEMONSTRA- |
| TED BY ACCEPTED ENGINEERING PRACTICES. |
| |
| 7) PROVIDE ENERGY CALCULATIONS AND |
| EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| AS REQUIRED BY THE 1997 FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILDING |
| CONSTRUCTION. |
| |
| 8)2305.2.2 FLOOR/CEILING ASSEMBLIES |
| SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/ |
| ING ASSEMBLIES SEPERATING USEABLE SPACE |
| INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| PING SHALL BE PROVIDED PARALLEL TO THE |
| MAIN FRAMING MEMBERS. |
| |
| 9) PLANS DO NOT INDICATE INSULATION |
| BENEATH THE 2ND FLOOR ABOVE THE GARAGE |
| CEILING. |
| |
| 10) PLANS INDICATE THE USE OF SEMCO |
| STRAPS, NO LONGER IN BUSINESS!THE SAME |
| WITH HUGHES PRODUCTS, DELETE THESE NOTES |
| ADD CURRENT MANUFACTURER & MODEL. |
| |
| 11)SHEET A-2 INDICATES THE UPLIFT VALUES |
| OF THE TRUSSES & GIRDERS, NO MANUFAC- |
| TURER INFORMATION OR MODEL NUMBER |
| SPECIFIED. |
| |
| 12) SHEET A-4 SECTION 1 TYPICAL 2-STORY: |
| TABLE 600 FOOTNOTE "I", THE FIRE RESIS- |
| TANCE REQUIREMENTS FOR EXTERIOR WALLS |
| WITH 5' OR LESS HORIZONTAL SEPERATION |
| SHALL BE BASED UPON BOTH INTERIOR AND |
| EXTERIOR FIRE EXPOSURES. |
| 709.6.2.2 THE FIRE RESISTANCE RATING OF |
| A WOOD FRAMED ASSEMBLY IS EQUAL TO THE |
| SUM OF THE TIME ASSIGNED TO THE MEMBRANE |
| ON THE FIRE EXPOSED SIDE, THE TIME |
| ASSIGNED TO THE FRAMING MEMBERS AND THE |
| TIME ASIGNED FOR ADDITIONAL CONTRIBUTION |
| BY OTHER PROTECTIVE MEASURES SUCH AS |
| INSULATION. THE MEMBRANE ON THE |
| UNEXPOSED SIDE SHALL NOT BE INCLUDED IN |
| DETERMINING THE FIRE RESISTANCE OF THE |
| ASSEMBLY. |
| THE TOTAL TIME WHEN ADDING THE 1/2" |
| DRYWALL, INSULATION & 2X4 FRAMING ADDS |
| UP TO 50 MINUTES (2ND FLOOR). BETWEEN |
| THE FIRST FLOORCEILING AND FLOOR OF THE |
| SECOND FLOOR NO INSULATION IS DETAILED, |
| HOW WILL THE 1 HR RATING BE ACHIEVED |
| FROM BOTH SIDES? |
| |
| 13) THIS SECOND FLOOR DETAIL NEEDS CLARI |
| FICATION, A CONTINIOUS LOAD PATH OF |
| RESISTANCE NEEDS TO BE ACHIEVED, USE A |
| CURRENT MANUFACTURER OF THE HURRICANE |
| RESISTANT STRAP, DELETE THE NOTE "STRAP |
| EMBEDDED 6" INTO CONCRETE 6"" WHERE WOOD |
| TO WOOD CONNECTIONS ARE REQUIRED! |
| THIS SAMEDETAIL INDICATES NO RIM |
| JOIST, BAND BOARD, WHAT WILL THE STRAPS |
| FROM THE STUDS FASTEN TO? CONTINIOUS |
| PATH! ALSO 2X4 BLOCKING, IF THE STUD |
| STRAPPING IS TO FASTEN TO THE BLOCKING, |
| HOW WILL CONTINIOUS PATH OCCUR? |
| |
| 14) SHEET A-2 NOTE# 3 THE ARCITECT OF |
| RECORD NTOES THAT"THE TRUSS BRACING ON |
| THIS PLAN SUPERSEDES THE BRACING SHOWN |
| ON THE TRUSS ENGINEERER'S SHOP DRAWINGS. |
| DOES THIS MEAN THERE IS A FAILURE DO TO |
| BRACING THE ARCHETECT SHALL RESUME |
| RESPONSIBILITY? A SECOND ISSUE WOULD BE |
| INSPECTIONS? |
| |
| 15) PLEASE INDICATE THE WALL HEIGTH BE- |
| HIND THE WATER CLOSET? 1203.2.6 EX(3) |
| DOES ALLOW MIN. 5'-0", SEE QUALIFYING |
| STATEMENT. |
| |
| 16)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 17) A COPY OF THE CALCULATED VALUE AND |
| ASSOCIATED PERMIT FEES ARE ATTACHED. |
| |
| 18) THE SIDE ENTRY WALL & GATE AS DEPICT |
| ED 5'-0" FROM THE BUILDING SHALL BE PART |
| OF THE BUILDING PERMIT, THERE IS NO |
| OTHER INFORMATION AS TO WHAT WILL OCCUR |
| AFTER THIS POINT! |
| |
| 19)PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| ANY QUESTIONS PLEASE CALL, |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| DEPARTMENT OF CONSTRUCTION SERVICES |
| CITY OF WEST PALM BEACH |
| (561) 659-8096 EXT. 8412 |