2002-06-08 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 02041951 |
| ADD: LOT# 31, SEC# 6, RENAISSANCE |
| CONT: HOME DYNAMICS CONST. CORP. |
| TEL: (954)520-1698 ( MIKE HANLEY) |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| ****BUILDING PROVISO**** |
| |
| |
| 1)FL BLDG 1909.3 (EXEPTION# 2) |
| CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| PORTED BY APPROVED MATERIALS OR SUPPORTS |
| AT SPACING NOT TO EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURER'S SPEC. |
| |
| 2)1804.1.3 THE BOTTOM OF THE FOUNDA- |
| TION SHALL EXTEND NO LESS THAN 12" |
| BELOW FINISH GRADE. |
| |
| 3) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| |
| 4) SH A-1 CENTER, BOTTOM OF PAGE DISCREP |
| ANCY, PLANS READ "CONFORM TO THE |
| 2001 FBC/ASCE 5-95" SHOULD READ 7-98. |
| |
| 5) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. |
| CLOSPAY OVERHEAD DOOR, HIGHLIGHT WHICH |
| MODEL SHALL BE USED FOR PRESSURE DESIGN. |
| MISSING FRONT ENTRY DOOR REPORT. |
| MISSING THE ROOFING ASSEMBLY REPORT ALSO |
| 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 6)1707.4.4.1 ANCHOR REQUIREMENTS: |
| WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR |
| ED IN ACCORDANCE WITH THE PUBLISHED |
| MANUFACTURER'S RECOMMENDATIONS TO |
| ACHIEVE THEDESIGN PRESSURE SPECIFIED. |
| SUBSTITUTE ANCHORING SYSTEM USED FOR |
| THE SUBSTRATE NOT SPECIFIED BY THE |
| FENESTRATION MANUFACTURER SHALL PROVIDE |
| EQUAL OR GREATER ANCHORING AS DEMONSTRA- |
| TED BY ACCEPTED ENGINEERING PRACTICES. |
| THE PRODUCT TESTING REPORTS INDICATE |
| A DIDDERENT ATTACHMENT METHOD FROM THAT |
| DESIGNED BY THE DESIGN PROFESSIONAL, |
| FOR WIDOWS DOORS AS WELL AS OVERHEAD GAR |
| AGE DOOR. |
| |
| 7) FL BLD CODE CHAP 13 ENERGY EFFICENCY |
| PROVIDE ENERGY CALS/ W MANUAL "J" |
| |
| 8)2305.2.2 FLOOR/CEILING ASSEMBLIES |
| SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/ |
| ING ASSEMBLIES SEPERATING USEABLE SPACE |
| INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| PING SHALL BE PROVIDED PARALLEL TO THE |
| MAIN FRAMING MEMBERS. |
| |
| 9) PLANS DO NOT DETAIL FLOOR INSULATION |
| BETWEEN THE 2ND FL LEVEL & THE GARAGE |
| CEILING. |
| |
| 10) PLANS INDICATE THE USE OF SEMCO |
| PRODUCTS, NO LONGER IN BUSINESS! THE |
| SAME HOLDS TRUE WITH HUGHES PRODUCTS, |
| DELETE NOTES & UPDATE MANUFACTURER AND |
| MODEL NUMBER, ALL REFRENCES. |
| 1707.3.1 JOIST HANGERS, FRAMING |
| ANCHORS & SIMILAR DEVICES SHALL BE TEST- |
| ED IN ACCORDANCE W/ ASTM D 1761 & BE |
| LABELED AND LISTED FOR THEIR LOAD CARRY- |
| ING CAPACITY. |
| |
| 11)A-2 INDICATES THE UPLIFT VALUES |
| OF THE TRUSSES & GIRDERS, NO MANUFACTUER |
| INFORMATION IS GIVEN FOR HOLD DOWN |
| DEVICES, INDICTE MANUFAC./ MODEL. |
| |
| 12) SHEET A-4 SECTION 1 TYPICAL 2-STORY, |
| TABLE600 FOOTNOTE "I", THE FIRE RESIS- |
| TANCE REQUIREMENTS FOR EXTERIOR WALLS |
| WITHIN 5'-0" OR LESS IN HORIZONTAL SEPER |
| ATION SHALL BE BASED UPON INTERIOR AND |
| EXTERIOR FIRE EXPOSURE. SEE 709.6.6.2 |
| FOR WOOD FRAME ASSEMBLY IS EQUAL TO THE |
| SUM OF THE TIME ASSIGNED TO THE MEMBRANE |
| ON THE FIRE EXPOSED SIDE, THE TIME |
| ASSIGNED TO THE FRAMING MEMBERS AND THET |
| IME ASSIGNED FOR ADDITIONAL CONTRIBUTION |
| BY OTHER PROTECTIVE MEASURES SUCH AS |
| INSULATION. THE MEMBRANE ON THE |
| UNEXPOSED SIDE SHALL NOT BE INCLUDED IN |
| DETERMINING THE FIRE RESISTANCE OF THE |
| ASSEMBLY. |
| THE TOTAL TIME WHEN ADDING THE 1/2" |
| DRYWALL, INSULATION & 2X4 FRAMING ADDS |
| UP TO 50 MINUTES(2ND FLOOR). BETWEEN THE |
| FIRST FLOOR CEILING AND FLOOR OF THE |
| SECOND FLOOR NO INSULATION IS DETAILED,( |
| REQUIRED FOR ENERGY CODE), HOW WILL THE |
| 1 HR RATING BE ACHIEVED FROM BOTH SIDES? |
| |
| 13) THIS SECOND FLOOR SAME SHEET AS |
| ABOVE, NEEDS CLARIFICATION, CONTINIOUS |
| LOAD PATH OF RESISTANCE NEEDS TO BE |
| ACHEIVED, USE A CURRENT MANUFACTURER OF |
| HURRICANE RESISTANT STRAP, DELETE NOTE |
| "STRAP EMBEDDED INTO CONCRETE 6" WHERE |
| A WOOD TO WOOD CONNECTIONS ARE REQUIRED! |
| THIS SAME DETAIL INDICATES NO RIM |
| JOIST, BAND BOARD, WHAT WILL THE STRAPSF |
| ROM THE STUDS 2ND FLOOR FASTEN TO? |
| CONTINIOUS PATH! ALSO 2X4 BLOCKING, IF |
| THE STUD STRAPPING IS TO BE FASTENED TO |
| THE BLOCKING, HOW SHALL CONTINIOUS PATH |
| OCCUR? |
| |
| 14) SHEET A-2 NOTE #3 THE ARCHETECT OF |
| RECORD NOTES THAT "THE TRUSS BRACING ON |
| THIS PLAN SUPERCEDES THE BRACING SHOWN |
| ON THE TRUSS ENGINEERS SHOP DRAWINGS. |
| DOES THIS MEAN IF THERE IS A FAILURE DO |
| TO BRACING THE ARCHETECT OF RECORD SHALL |
| RESUME RESPONSIBILITY? ASECOND ISSUE |
| WOULD BE INSPECTIONS? |
| |
| 15)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 16)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 17) A COPY OF THE CALCULATED VALUE AND |
| ASSOCIATED PERMIT FEES ARE ATTACHED. |
| |
| ANY QUESTIONS PLEASE CALL, |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| DEPARTMENT OF CONSTRUCTION SERVICES |
| CITY OF WEST PALM BEACH |
| (561) 659-8096 EXT. 8412 |