| BUILDING PLAN REVIEW |
| PERMIT: 02041948 |
| ADD:RENAISSANCE/ SEC6 LOT 34 |
| CONT: HOME DYNAMICS CONSTRUCTION |
| TEL: (954) 484-4800 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)- FL BLDG 1909.3 (EXEPTION# 2) |
| CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| PORTED BY APPROVED MATERIALS OR SUPPORTS |
| AT SPACING NOT TO EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURER'S SPEC. |
| |
| 2)- 1804.1.3 THE BOTTOM OF THE FOUNDA- |
| TION SHALL EXTEND NO LESS THAN 12" |
| BELOW FINISH GRADE. THE SECTION QUOTED |
| ON SHEET A-3 WALL SECTION 8" MIN. PER |
| FBC 1821.1.1 IS A HIGH WIND SECTION OF |
| THE CODE THAT DEALS WITH DADE & BROWARD |
| COUNTIES. |
| |
| 3) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| FL STATE STAT. 61G 15-23.002 A PROFESS- |
| IONAL ENGINEER SHALL SIGN HIS NAME AND |
| AFFIX HIS SEAL TO ALL PLANS, REPORTS FOR |
| PUBLIC RECORD. |
| IN REGARDS TO THE REPORT SUBMITTED |
| PAGE 2 OF 9 INDICATES THAT "THE INFORMAT |
| ION PROVIDED IN THIS REPORT IS NOT SUFF- |
| ICIENT FOR A FINAL DESIGN OF THE FOUNDA- |
| TION SYSTEM. PAGE 9 OF 9, LIMITATIONS, |
| RESTATES NOT SUFFICIENT FOR A FINAL |
| DESIGN OF THE FOUNDATION SYSTEM. |
| |
| 4)- SHEET A-1 LOWER LEFT DISCREPANCY, |
| PLANS CONFORM TO 2001 FLB/ ASCE 5-95 |
| SHOULD READ ASCE 7-98 |
| |
| 5) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. |
| A) DESIGNATE AS TO WHICH MODEL OVER- |
| HEAD CLOSPAY GARAGE DOOR SHALL BE USED |
| AND THE DESIGN LOADS OF THE UNIT. |
| INDICATE HOW PRODUCT TESTING ACCOMPLISH- |
| ED WITH 60 " SQ VENT? |
| B) MISSING REPORT FOR THE FRONT ENTRY |
| DOOR. DADE COUNTY OR SBCCI REPORT, (2) |
| COPIES, (3) FOR RESIDENT INSPECTOR |
| PROGRAM. |
| C) MISSING REPORT FOR ROOFING ASSEMB- |
| LIES, DADE COUNTY OR SBCCI REPORTS. |
| D)PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS.DADE COUNTY |
| OR SBCCI REPORTS. |
| |
| 6) 1707.4.4.1 ANCHORING REQUIREMENTS, |
| WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR |
| ED IN ACCORDANCE WITH THE PUBLISHED |
| MANUFACTURER'S RECOMMENDATIONS TO |
| ACHIEVE THE DESIGN PRESSURE SPECIFIED. |
| SUBSTITUTE ANCHORING SYSTEMS USED FOR |
| THE SUBSTRATES NOT SPECIFIED BY THE |
| FENESTRATION MANUFACTURER SHALL PROVIDE |
| EQUAL OR GREATER ANCHORING AS DEMONSTRA- |
| TED BY ACCEPTED ENGINEERING PRACTICES. |
| |
| 7) PROVIDE ENERGY CALCULATIONS AND |
| EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| AS REQUIRED BY THE 1997 FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILDING |
| CONSTRUCTION. |
| |
| 8) PROVIDE INFORMATION FRONT GABLE, IS |
| THW GABLE WALL FRAME OR BLOCK? |
| |
| 9) SHEET A-3 INDICATES THE USE OF A |
| SEMCO STRAP, NO LONGER IN BUSINESS! |
| |
| 10)SHEET A-1 INDICATES THE UPLIFT VALUES |
| OF THE TRUSSES & GIRDERS, NO MANUFAC- |
| TUER OR MODEL NUMBER IS SPECIFIED. |
| |
| 11) 2309.7.1 VENTILATION OF ATTIC SPACE |
| PROVIDE INFO. |
| |
| 12)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 13)PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| ANY QUESTIONS PLEASE CALL, |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| DEPARTMENT OF CONSTRUCTION SERVICES |
| CITY OF WEST PALM BEACH |
| (561) 659-8096 EXT. 8412 |