2002-04-30 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT# 02041858 |
| 1501 N AUSTRALIAN AV |
| CONT: WHITING- TURNER |
| TEL: 718-2367 |
| |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)- PLANS SUBMITTED AFTER FEB. 28,2002 |
| SHALL BE DESIGNED & REVIEWED UNDER THE |
| 2001 FL. BUILDING CODE, NOT THE 97 SBC. |
| |
| 2)- FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 3)- FOOT BRIDGE- TABLE 1604.1 LIVE LOADS |
| INDICATE WHAT LOADS THE FOOT BRIDGE IS |
| DESIGNED TO? |
| |
| 4)- FL BLD CODE 1604.9 SIDEWLKS SHALL BE |
| DESIGNED TO CARRY EITHER A UNIFORM DIS- |
| TRIBUTED LOAD OF 200LBS OR A CONCENTRA- |
| TED LOAD OF 8,000 LBS ON A SPACE 2 1/2 |
| SQ FT AND PLACED IN ANY POSITION, WHICH- |
| EVER WILL PRODUCE THE GREATER STRESS. |
| |
| 5)- SHEET P-1 INDICATES MONUMENTAL |
| STAIRS ENTERING THE POOL PAVILION, TWO |
| ISSUES ARE TO BE CLARIFIED, HANDICAPPED |
| EGRESS? SINCE A SITE PLAN WAS NOT ENCLUD |
| ED WE ARE ASSUMING THAT THE 6"-0" WALK- |
| WAY MEETS THE FL. ACCESSIBILITY REQUIRE- |
| MENTS. THE SECOND ISSUE WILL BE THE RE- |
| QUIREMENT FOR INTERMEDIATE HANDRAILS. FL |
| BLD CODE 1007.5.7 HANDRAILS SHALL BE PRO |
| VIDED WITHIN 30" OF ALL PORTIONS OF THE |
| STAIR WIDTH REQUIRED FOR EGRESS CAPACITY |
| IN ACCORDANCE WITH TABLE 1004. THE |
| REQUIRED EGRESS WIDTH SHALL BE ALONG THE |
| NATURAL PATH OF TRAVEL. THE CODE COMMEN |
| TARY DOES GIVE SOME LATITUDE IN THE RE- |
| QUIRED DIMENSIOIN BETWEEN HANDRAILS. THE |
| MAIN CRITERIA IS WHAT IS THE OCCUPANT |
| LOAD FOR THIS STAIRWAY? WILL THE (2) |
| NEW HANDRAILS GIVE US ADEQUATE ACCESS |
| AS REQUIRED UNDER TABLE 1004? SEE ATTACH |
| MENT. |
| |
| 6)- MISSING INFORMATION ON SHELTER TO |
| BE MOVED? |
| |
| SHEET AD-2 |
| 7)- 11-4.1.3(1) AT LEAST ONE ACCESSIBLE |
| ROUTTE COMPLYING WITH 11-4.3 SHALL |
| CONNECT ACCESSIBLE BUILDING OR FACILITY |
| ENETRANCES WITH ALL ACCESSIBLE SPACES |
| AND ELEMENTS WITHIN THE BUILDING OR |
| FACILITY. |
| 11-4.1.3(3) GROUND & FLOOR SURFACES |
| ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE |
| ROOMS & SPACES SHALL COMPLY WITH |
| 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) |
| A STATIC COEFFICIENT OF FRICTION OF 0.6 |
| IS RECOMENDED FOR ACCESSIBLE ROUTES |
| AND 0.8 FOR RAMPS. |
| THE AREAS IN AND AROUND THE PLAY- |
| GROUND ARE TO BE ACCESSIBLE FOR WHEEL- |
| CHAIRS, AD-4 SEC 5 INDICATES THE USE OF |
| MULCH AS A FIRM SURFACE, PLEASE PROVIDE |
| ADDITIONAL DATA. THE FLORIDA ACCESSIBL- |
| ITY CODE GIVES THE LAW AS TO WHAT CAN & |
| CAN'T BE USED. THERE IS FEDERAL GUIDE- |
| LINE ADA ACCESSIBILITY GUIDELINES FOR |
| PLAY AREAS. IN THE GUIDELINE IT GIVES |
| TERMS, AND STANDARDS. FOR EXAMPLE,"USE |
| ZONE" THE GROUND LEVEL BENEATH AND IMMED |
| IATELY ADJACENT TO A PLAY STRUCTURE OR |
| PIECE OF EQUIPMENT THAT IS DESIGNED BY |
| ASTM F 1487 STANDARD CONSUMER SAFETY |
| PERFORANCE SPECIFICATION FOR PLAYGROUND |
| EQUIPMENT FOR PUBLIC USE FOR UNRESTRICT- |
| ED CIRCULATION. |
| THIS GUIDELINE ALSO SHALL INDICATE |
| THE RATIO OF PLAYGROUND EQUIPMENT THAT |
| NEEDS TO BE ACCESSIBILE. |
| PLANS STATE THAT THE PLAYGROUND |
| EQUIPMENT WILL BE PERMITED SEPERATELY, |
| THESE ELEMENTS SHALL BE ADDRESSED. |
| |
| 8) SHEET AD-6 OVERLOOK TOWER NOT ACCESSI |
| BLE 11-4.1.2 VERTICAL ACCESSIBILITY, |
| NOTHING IN THIS CODE SHALL BE CONSTRUED |
| TO RELIEVE THE OWNER OF ANY BUILDING, |
| SSTRUCTURE OR FACILITY FROM THE DUTY TO |
| PROVIDE VERTICAL ACCESSIBILITY TO ALL |
| LEVELS ABOVE OR BELOW THE OCCUPIAABLE |
| GRADE LEVEL. |
| S |
| |