Plan Review Notes For Permit 02041777 |
Permit Number |
02041777 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-16 00:00:00 | PLAN DENIED | | #1 DUCT SIZE IN RISER DO NOT MATCH | | FROM 1ST TO 2ED FLOOR | | #2 VARIFY VENTILATION 401 NATURAL OR | | 402 MECHANICAL | | #3 NEED CALCULATIONS ON TYPE OF | | VENTILATION USER | | #4 CHANGE EQUIPMENT SIZE ON PLAN TO 5 | | #5 COPPER SIZE MUST MEET MANUFACTURER'S | | INSTALLATIONS INSTRUCTIONS | | PLAM REVIEW BY HAROLD MOSER | | [561]659-8096 EXT 8390 |
|