2002-06-25 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT ON THE PLANS AS
 REQUIRED BY THE 2001 FBC SEC. 1606.1.7.
  
 3) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 4) PROVIDE SOIL BEARING TEST REPORT PER
 CITY OF WPB AMENDMENTS TO 2001 FBC SEC.
 1804.2.2.
  
 5) PROVIDE (2) COPIES OF INSTALLATION
 SCHEDULE FOR STORM PANELS. THESE ITEMS
 ARE REQUIRED AT TIME OF PERMIT OR YOU
 WILL BE REQUIRED TO PULL A SEPARATE
 PERMIT WITH ADDITIONAL FEES.
  
 6) PROVIDE ADDITIONAL COPIES OF PRODUCT
 APPROVALS FOR THE FRONT DOOR AND GLASS
 BLOCK. TWO COPIES ARE REQUIRED.
  
 7) PROVIDE TESTING INFORMATION WHICH
 INDICATES THAT THE GLASS BLOCK HAS A
 FIRE RATING OF ONE HOUR.
  
 8) PLEASE CHANGE THE CALL SIZE OF THE
 EGRESS WINDOW (I) IN THE WINDOW SCHEDULE
 TO 24/5 SH WHICH CORRESPONDS TO THE
 DIMENSIONS GIVEN.
  
 9) PLEASE CHANGE NOTE #6 UNDER GENERAL
 NOTES ON A2 TO REFERENCE THE 2001
 FLORIDA PLUMBING CODE.
  
 10) PROVIDE A DETAIL INDICATING ONE HOUR
 FIRE RATED ASSEMBLY BASED ON BOTH
 INTERIOR AND EXTERIOR FIRE EXPOSURE FOR
 THE GABLE END ON THE ZERO LOT LINE.
  
 11) PLEASE INSERT THE REVISED SHEETS
 INTO THE PLANS. SUBMIT THE OLD SHEETS
 ALONG WITH THE PLANS.
  