Plan Review Notes
Plan Review Notes For Permit 02041773
Permit Number 02041773
Review Stop M
Sequence Number 1
Notes
Date Text
2002-05-11 00:00:00PLAN DENIED
 #1 DUCT SIZE FROM 1ST & 2ED FLOOR DO NOT
 MATCH
 #2 CHANGE AIRCONDITIONING EQUIPMENT
 ON PLAN TO 5 TON
 #3 CHANGE COPPER SIZE TO MANUFACTURER'S
 INSTALLATIONS INSTURCTIONS
 #4 SHOW TYPE OF VENTILATION
 #5 NEED CALCULATIONS FOR VENTILATION
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390