2002-05-15 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE PLANS REFERENCES
 CODES FROM 96 NEC. PLEASE NOTE CODES
 FROM 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT FOR 22.00
 AIC RATING ON RISER DIAGRAM.
  
 3)NOTE: PLEASE NOTE MISSINGARC FAULT
 PROTECTION PER 210-12.
  
 4 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  