Plan Review Notes
Plan Review Notes For Permit 02041770
Permit Number 02041770
Review Stop P
Sequence Number 2
Notes
Date Text
2002-06-13 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FROM PREVIOUS REVIEW - ENGINEERS RE-
 PORT ON CALCULATIONS FOR 1" VENT ARE FOR
 A 1HP PUMP, A 2HP PUMP IS BEING USED.
 SUBMIT CALCUALTIONS FOR A 2" PUMP OR USE
 1-1/2" VENT LINES.
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)FROM PREV-
 IOUS REVIEW.
 3) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 FROM PREVIOUS REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377